Współczynnik korekcyjny

Współczynniki korekcyjne dla grzejników ściennych REGULUS-system REGULLUS

temperatura pomieszczenia
tztp581216202224
95900.5750.5950.6240.6560.6920.7110.731
850.5920.6130.6440.6780.7160.7370.758
800.6090.6320.6650.7010.7420.7640.788
750.6280.6520.6870.7260.7700.7940.819
700.6480.6740.7110.7530.8000.8260.854
90850.6100.6330.6650.7020.7430.7650.788
800.6290.6530.6880.7270.7710.7950.820
750.6490.6740.7120.7540.8010.8270.854
700.6700.6970.7370.7820.8340.8620.892
650.6920.7220.7650.8140.8690.90.933
85800.6490.6750.7120.7540.8020.8280.855
750.6710.6980.7380.7830.8340.8630.893
700.6930.7220.7660.8140.8700.9010.934
650.7170.7490.7950.8480.9090.9420.978
600.7430.7770.8280.8850.9510.9881.028
80750.6940.7230.7670.8150.8710.9020.935
700.7180.7500.7960.8490.9100.9430.980
650.7440.7780.8290.8860.9520.9891.029
600.7720.8090.8640.9260.9991.0401.084
550.8030.8420.9020.9701.0501.0961.145
75700.7450.7790.830.8870.9530.9901.mar
650.7730.8100.8650.9271.0001.0411.085
600.8040.8430.9030.9711.0521.0971.146
550.8360.8790.9441.0201.1091.1591.215
500.8720.9190.9901.0741.1731.2291.292
70650.8050.8440.9040.9731.0531.0981.148
600.8370.8810.9461.0211.1101.1611.216
550.8730.9200.9921.0751.1741.2311.294
500.9120.9641.0421.1351.2461.3101.382
450.9551.0111.0981.2021.3271.4011.483
65600.8740.9210.9931.0771.1761.2331.295
550.9130.9651.0441.1361.2481.3121.383
500.9561.0131.1001.2041.3291.4031.485
60550.9571.0141.1011.2051.3311.4051.487
501.0041.0671.1641.2811.4241.5091.604
451.0561.1261.2341.3671.5321.6301.742
401.1131.1911.3141.4651.6571.7721.906
55501.0581.1271.2361.3691.5341.6331.745
451.1151.1931.3161.4681.6591.7751.909
401.1791.2671.4071.5821.8071.9462.108
351.2521.3511.5111.7151.9842.1532.354
50451.1821.2691.4091.5851.8101.9492.112
401.2541.3531.5141.7181.9872.1572.358
351.3361.4491.6361.8772.2042.4142.670
301.429sty.561.7782.0692.4732.7423.078
45401.3381.4521.6391.8812.2082.4192.675
351.4321.5631.7822.0732.4782.7483.084
301.5401.6931.9532.3082.8243.1813.642
40351.5431.6971.9572.3142.8313.188mar.65
301.6691.8512.1662.6113.2923.7884.462

LEGENDA:
tz – temperatura zasilania
tp – temperatura powrotu

W opisie parametrów grzejnika tz występuje jako pierwsza wartość, tp jako druga, a tempertura pomieszczenia jako trzecia, np. 55/45/20

Aby obliczyć moc grzewczą dla niestandardowych parametrów zasilania należy podzielić moc grzewczą dla parametru 75/65/20 przez wartość odczytaną z tabeli współczynników korekcyjnych.
Np. Szukamy mocy grzewczej dla grzejnika S6/60 dla parametru 70/50/20. Moc dla 75/65/20 wynosi 922 W. W tabeli współczynników korekcyjnych odczytujemy wartość współczynnika dla: tz = 70, tp = 50, temperatura pomieszczenia = 20. Dla tych parametrów współczynnik wynosi: 1,246.
Zatem: 922/1,246 ≈740 W

Współczynniki korekcyjne dla grzejników ściennych REGULUS-system SOLLARIUS

temperatura pomieszczenia
tztp581216202224
95900.5750.5950.6240.6560.6920.7110.731
850.5920.6130.6440.6780.7160.7370.758
800.6090.6320.6650.7010.7420.7640.788
750.6280.6520.6870.7260.7700.7940.819
700.6480.6740.7110.7530.8000.8260.854
90850.6100.6330.6650.7020.7430.7650.788
800.6290.6530.6880.7270.7710.7950.820
750.6490.6740.7120.7540.8010.8270.854
700.6700.6970.7370.7820.8340.8620.892
650.6920.7220.7650.8140.8690.90.933
85800.6490.6750.7120.7540.8020.8280.855
750.6710.6980.7380.7830.8340.8630.893
700.6930.7220.7660.8140.8700.9010.934
650.7170.7490.7950.8480.9090.9420.978
600.7430.7770.8280.8850.9510.9881.028
80750.6940.7230.7670.8150.8710.9020.935
700.7180.7500.7960.8490.9100.9430.980
650.7440.7780.8290.8860.9520.9891.029
600.7720.8090.8640.9260.9991.0401.084
550.8030.8420.9020.9701.0501.0961.145
75700.7450.7790.830.8870.9530.9901.mar
650.7730.8100.8650.9271.0001.0411.085
600.8040.8430.9030.9711.0521.0971.146
550.8360.8790.9441.0201.1091.1591.215
500.8720.9190.9901.0741.1731.2291.292
70650.8050.8440.9040.9731.0531.0981.148
600.8370.8810.9461.0211.1101.1611.216
550.8730.9200.9921.0751.1741.2311.294
500.9120.9641.0421.1351.2461.3101.382
450.9551.0111.0981.2021.3271.4011.483
65600.8740.9210.9931.0771.1761.2331.295
550.9130.9651.0441.1361.2481.3121.383
500.9561.0131.1001.2041.3291.4031.485
60550.9571.0141.1011.2051.3311.4051.487
501.0041.0671.1641.2811.4241.5091.604
451.0561.1261.2341.3671.5321.6301.742
401.1131.1911.3141.4651.6571.7721.906
55501.0581.1271.2361.3691.5341.6331.745
451.1151.1931.3161.4681.6591.7751.909
401.1791.2671.4071.5821.8071.9462.108
351.2521.3511.5111.7151.9842.1532.354
50451.1821.2691.4091.5851.8101.9492.112
401.2541.3531.5141.7181.9872.1572.358
351.3361.4491.6361.8772.2042.4142.670
301.429sty.561.7782.0692.4732.7423.078
45401.3381.4521.6391.8812.2082.4192.675
351.4321.5631.7822.0732.4782.7483.084
301.5401.6931.9532.3082.8243.1813.642
40351.5431.6971.9572.3142.8313.188mar.65
301.6691.8512.1662.6113.2923.7884.462

LEGENDA:
tz – temperatura zasilania
tp – temperatura powrotu

W opisie parametrów grzejnika tz występuje jako pierwsza wartość, tp jako druga, a tempertura pomieszczenia jako trzecia, np. 55/45/20

Aby obliczyć moc grzewczą dla niestandardowych parametrów zasilania należy podzielić moc grzewczą dla parametru 75/65/20 przez wartość odczytaną z tabeli współczynników korekcyjnych.
Np. Szukamy mocy grzewczej dla grzejnika S6/60 dla parametru 70/50/20. Moc dla 75/65/20 wynosi 922 W. W tabeli współczynników korekcyjnych odczytujemy wartość współczynnika dla: tz = 70, tp = 50, temperatura pomieszczenia = 20. Dla tych parametrów współczynnik wynosi: 1,246.
Zatem: 922/1,246 ≈740 W

Współczynniki korekcyjne dla grzejników ściennych REGULUS-system DUBEL

temperatura pomieszczenia
tztp581216202224
95900.5750.5950.6240.6560.6920.7110.731
850.5920.6130.6440.6780.7160.7370.758
800.6090.6320.6650.7010.7420.7640.788
750.6280.6520.6870.7260.7700.7940.819
700.6480.6740.7110.7530.8000.8260.854
90850.6100.6330.6650.7020.7430.7650.788
800.6290.6530.6880.7270.7710.7950.820
750.6490.6740.7120.7540.8010.8270.854
700.6700.6970.7370.7820.8340.8620.892
650.6920.7220.7650.8140.8690.90.933
85800.6490.6750.7120.7540.8020.8280.855
750.6710.6980.7380.7830.8340.8630.893
700.6930.7220.7660.8140.8700.9010.934
650.7170.7490.7950.8480.9090.9420.978
600.7430.7770.8280.8850.9510.9881.028
80750.6940.7230.7670.8150.8710.9020.935
700.7180.7500.7960.8490.9100.9430.980
650.7440.7780.8290.8860.9520.9891.029
600.7720.8090.8640.9260.9991.0401.084
550.8030.8420.9020.9701.0501.0961.145
75700.7450.7790.830.8870.9530.9901.mar
650.7730.8100.8650.9271.0001.0411.085
600.8040.8430.9030.9711.0521.0971.146
550.8360.8790.9441.0201.1091.1591.215
500.8720.9190.9901.0741.1731.2291.292
70650.8050.8440.9040.9731.0531.0981.148
600.8370.8810.9461.0211.1101.1611.216
550.8730.9200.9921.0751.1741.2311.294
500.9120.9641.0421.1351.2461.3101.382
450.9551.0111.0981.2021.3271.4011.483
65600.8740.9210.9931.0771.1761.2331.295
550.9130.9651.0441.1361.2481.3121.383
500.9561.0131.1001.2041.3291.4031.485
60550.9571.0141.1011.2051.3311.4051.487
501.0041.0671.1641.2811.4241.5091.604
451.0561.1261.2341.3671.5321.6301.742
401.1131.1911.3141.4651.6571.7721.906
55501.0581.1271.2361.3691.5341.6331.745
451.1151.1931.3161.4681.6591.7751.909
401.1791.2671.4071.5821.8071.9462.108
351.2521.3511.5111.7151.9842.1532.354
50451.1821.2691.4091.5851.8101.9492.112
401.2541.3531.5141.7181.9872.1572.358
351.3361.4491.6361.8772.2042.4142.670
301.429sty.561.7782.0692.4732.7423.078
45401.3381.4521.6391.8812.2082.4192.675
351.4321.5631.7822.0732.4782.7483.084
301.5401.6931.9532.3082.8243.1813.642
40351.5431.6971.9572.3142.8313.188mar.65
301.6691.8512.1662.6113.2923.7884.462

LEGENDA:
tz – temperatura zasilania
tp – temperatura powrotu

W opisie parametrów grzejnika tz występuje jako pierwsza wartość, tp jako druga, a tempertura pomieszczenia jako trzecia, np. 55/45/20

Aby obliczyć moc grzewczą dla niestandardowych parametrów zasilania należy podzielić moc grzewczą dla parametru 75/65/20 przez wartość odczytaną z tabeli współczynników korekcyjnych.
Np. Szukamy mocy grzewczej dla grzejnika S6/60 dla parametru 70/50/20. Moc dla 75/65/20 wynosi 922 W. W tabeli współczynników korekcyjnych odczytujemy wartość współczynnika dla: tz = 70, tp = 50, temperatura pomieszczenia = 20. Dla tych parametrów współczynnik wynosi: 1,246.
Zatem: 922/1,246 ≈740 W

Współczynniki korekcyjne dla grzejników ściennych REGULUS-system E-VENT

Temperatura pomieszczenia
tztp581216202224
95900.5830.6030.6320.6630.6990.7180.738
850.5990.6200.6510.6850.7230.7430.765
800.6170.6390.6720.7080.7480.7700.794
750.6350.6590.6940.7330.7760.8060.825
700.6550.6810.7180.7590.8060.8320.859
90850.6170.6390.6720.7080.7480.7700.794
800.6350.6590.6940.7330.7760.8060.825
750.6550.6810.7180.7590.8060.8320.859
700.6760.7030.7430.7880.8390.8660.896
650.6990.7280.7700.8190.8740.9040.937
85800.6550.6810.7180.7590.8060.8320.859
750.6760.7030.7430.7880.8660.896
700.6990.7280.7700.8190.8740.9040.937
650.7230.7540.8000.8520.9120.9450.981
600.7480.7820.8320.8890.9540.9901.030
80750.6990.7280.7700.8190.8740.9040.937
700.7230.7540.8000.8520.9120.9450.981
650.7480.7820.8320.8890.9540.9901.030
600.7760.8120.8660.9281.0001.0401.083
550.8060.8450.9040.9721.0501.0951.143
75700.7480.7820.8320.8890.9540.9901.030
650.7760.8120.8660.9281.0401.083
600.8060.8450.9040.9721.0501.0951.143
550.8390.8810.9451.0191.1071.1561.211
500.8740.9200.9901.0721.1691.2251.286
70650.8060.8450.9040.9721.0501.0951.143
600.8390.8810.9451.0191.1071.1561.211
550.8740.9200.9901.0721.1691.2251.286
500.9120.9631.0401.1311.2401.3031.373
450.9541.0091.0951.1971.3201.3911.471
65600.8740.9200.9901.0721.1691.2251.286
550.9120.9631.0401.1311.2401.3031.373
500.9541.0091.0951.1971.3201.3911.471
60550.9541.0091.0951.1971.3201.3911.471
501.0001.0611.1561.2711.4101.4931.585
451.0501.1191.2251.3541.5151.6111.719
401.1071.1831.3031.4501.6361.7491.879
55501.0501.1191.2251.3541.5151.6111.719
451.1071.1831.3031.4501.7491.879
401.1691.2551.3911.5611.7801.9142.071
351.2401.3371.4931.6911.9512.1152.308
50451.1691.2551.3911.5611.7801.9142.071
401.2401.3371.4931.6911.9512.1152.308
351.3201.4301.6111.8442.1602.3632.609
301.4101.5381.7492.0292.4202.6793.001
45401.3201.431.6111.8442.1602.3632.609
351.4101.5381.7492.0292.4202.6793.001
301.5151.6631.9142.2572.7523.0943.535
40351.5151.6631.9142.2572.7523.0943.535
301.6361.8112.1152.5423.1943.6664.307

LEGENDA:
tz – temperatura zasilania
tp – temperatura powrotu

W opisie parametrów grzejnika tz występuje jako pierwsza wartość, tp jako druga, a tempertura pomieszczenia jako trzecia, np. 55/45/20

Aby obliczyć moc grzewczą dla niestandardowych parametrów zasilania należy podzielić moc grzewczą dla parametru 75/65/20 przez wartość odczytaną z tabeli współczynników korekcyjnych.
Np. Szukamy mocy grzewczej dla grzejnika S6/60 dla parametru 70/50/20. Moc dla 75/65/20 wynosi 922 W. W tabeli współczynników korekcyjnych odczytujemy wartość współczynnika dla: tz = 70, tp = 50, temperatura pomieszczenia = 20. Dla tych parametrów współczynnik wynosi: 1,246.
Zatem: 922/1,246 ≈740 W

Współczynniki korekcyjne dla grzejników ściennych REGULUS-system REVERS

Temperatura pomieszczenia
tztp581216202224
95900.5830.6030.6320.6630.6990.7180.738
850.5990.6200.6510.6850.7230.7430.765
800.6170.6390.6720.7080.7480.7700.794
750.6350.6590.6940.7330.7760.8060.825
700.6550.6810.7180.7590.8060.8320.859
90850.6170.6390.6720.7080.7480.7700.794
800.6350.6590.6940.7330.7760.8060.825
750.6550.6810.7180.7590.8060.8320.859
700.6760.7030.7430.7880.8390.8660.896
650.6990.7280.7700.8190.8740.9040.937
85800.6550.6810.7180.7590.8060.8320.859
750.6760.7030.7430.7880.8660.896
700.6990.7280.7700.8190.8740.9040.937
650.7230.7540.8000.8520.9120.9450.981
600.7480.7820.8320.8890.9540.9901.030
80750.6990.7280.7700.8190.8740.9040.937
700.7230.7540.8000.8520.9120.9450.981
650.7480.7820.8320.8890.9540.9901.030
600.7760.8120.8660.9281.0001.0401.083
550.8060.8450.9040.9721.0501.0951.143
75700.7480.7820.8320.8890.9540.9901.030
650.7760.8120.8660.9281.0401.083
600.8060.8450.9040.9721.0501.0951.143
550.8390.8810.9451.0191.1071.1561.211
500.8740.9200.9901.0721.1691.2251.286
70650.8060.8450.9040.9721.0501.0951.143
600.8390.8810.9451.0191.1071.1561.211
550.8740.9200.9901.0721.1691.2251.286
500.9120.9631.0401.1311.2401.3031.373
450.9541.0091.0951.1971.3201.3911.471
65600.8740.9200.9901.0721.1691.2251.286
550.9120.9631.0401.1311.2401.3031.373
500.9541.0091.0951.1971.3201.3911.471
60550.9541.0091.0951.1971.3201.3911.471
501.0001.0611.1561.2711.4101.4931.585
451.0501.1191.2251.3541.5151.6111.719
401.1071.1831.3031.4501.6361.7491.879
55501.0501.1191.2251.3541.5151.6111.719
451.1071.1831.3031.4501.7491.879
401.1691.2551.3911.5611.7801.9142.071
351.2401.3371.4931.6911.9512.1152.308
50451.1691.2551.3911.5611.7801.9142.071
401.2401.3371.4931.6911.9512.1152.308
351.3201.4301.6111.8442.1602.3632.609
301.4101.5381.7492.0292.4202.6793.001
45401.3201.431.6111.8442.1602.3632.609
351.4101.5381.7492.0292.4202.6793.001
301.5151.6631.9142.2572.7523.0943.535
40351.5151.6631.9142.2572.7523.0943.535
301.6361.8112.1152.5423.1943.6664.307

LEGENDA:
tz – temperatura zasilania
tp – temperatura powrotu

W opisie parametrów grzejnika tz występuje jako pierwsza wartość, tp jako druga, a tempertura pomieszczenia jako trzecia, np. 55/45/20

Aby obliczyć moc grzewczą dla niestandardowych parametrów zasilania należy podzielić moc grzewczą dla parametru 75/65/20 przez wartość odczytaną z tabeli współczynników korekcyjnych.
Np. Szukamy mocy grzewczej dla grzejnika S6/60 dla parametru 70/50/20. Moc dla 75/65/20 wynosi 922 W. W tabeli współczynników korekcyjnych odczytujemy wartość współczynnika dla: tz = 70, tp = 50, temperatura pomieszczenia = 20. Dla tych parametrów współczynnik wynosi: 1,246.
Zatem: 922/1,246 ≈740 W

Współczynniki korekcyjne dla grzejników dekoracyjnych REGULUS-system DECOR

temperatura pomieszczenia
tztp581216202224
95900,490,510,550,580,620,650,67
850,510,530,570,610,650,680,70
800,530,550,590,630,680,710,74
750,550,580,620,660,720,750,78
700,570,600,650,700,750,780,82
90850,530,550,590,630,680,710,74
800,550,580,620,660,720,750,78
750,570,600,650,700,750,780,82
700,600,630,680,730,790,830,87
650,620,660,710,770,840,880,92
85800,570,600,650,700,750,780,82
750,600,630,680,730,790,830,87
700,620,660,710,770,840,880,92
650,650,690,750,810,890,930,98
600,680,720,780,860,940,991,04
80750,620,660,710,770,840,880,92
700,650,690,750,810,890,930,98
650,680,720,780,860,940,991,04
600,720,760,830,911,001,051,11
550,750,800,880,961,071,131,19
75700,680,720,780,860,940,991,04
650,720,760,830,911,001,051,11
600,750,800,880,961,071,131,19
550,790,850,931,031,141,211,29
500,840,900,991,101,231,311,39
70650,750,800,880,961,071,131,19
600,790,850,931,031,141,211,29
550,840,900,991,101,231,311,39
500,890,951,051,181,331,421,52
450,941,011,131,271,441,541,66
65600,840,900,991,101,231,311,39
550,890,951,051,181,331,421,52
500,941,011,131,271,441,541,66
451,001,081,211,371,571,691,84
60550,941,011,131,271,441,541,66
501,001,081,211,371,571,691,84
451,071,161,311,491,731,872,04
401,141,251,421,631,912,092,29
55501,071,161,311,491,731,872,04
451,141,251,421,631,912,092,29
401,231,351,541,802,142,352,61
351,331,471,692,002,412,683,01
50451,231,351,541,802,142,352,61
401,331,471,692,002,412,683,01
351,441,601,872,242,763,103,53
301,571,762,092,543,203,664,25
45401,441,601,872,242,763,103,53
351,571,762,092,543,203,664,25
301,731,952,352,923,794,435,27
40351,731,952,352,923,794,435,27
301,912,192,683,424,615,536,84

LEGENDA:
tz – temperatura zasilania
tp – temperatura powrotu

W opisie parametrów grzejnika tz występuje jako pierwsza wartość, tp jako druga, a tempertura pomieszczenia jako trzecia, np. 55/45/20

Aby obliczyć moc grzewczą dla niestandardowych parametrów zasilania należy podzielić moc grzewczą dla parametru 75/65/20 przez wartość odczytaną z tabeli współczynników korekcyjnych.
Np. Szukamy mocy grzewczej dla grzejnika S6/60 dla parametru 70/50/20. Moc dla 75/65/20 wynosi 922 W. W tabeli współczynników korekcyjnych odczytujemy wartość współczynnika dla: tz = 70, tp = 50, temperatura pomieszczenia = 20. Dla tych parametrów współczynnik wynosi: 1,246.
Zatem: 922/1,246 ≈740 W

Współczynniki korekcyjne dla grzejników dekoracyjnych REGULUS-system TOWER VENT

temperatura pomieszczenia
tztp581216202224
95900,490,510,550,580,620,650,67
850,510,530,570,610,650,680,70
800,530,550,590,630,680,710,74
750,550,580,620,660,720,750,78
700,570,600,650,700,750,780,82
90850,530,550,590,630,680,710,74
800,550,580,620,660,720,750,78
750,570,600,650,700,750,780,82
700,600,630,680,730,790,830,87
650,620,660,710,770,840,880,92
85800,570,600,650,700,750,780,82
750,600,630,680,730,790,830,87
700,620,660,710,770,840,880,92
650,650,690,750,810,890,930,98
600,680,720,780,860,940,991,04
80750,620,660,710,770,840,880,92
700,650,690,750,810,890,930,98
650,680,720,780,860,940,991,04
600,720,760,830,911,001,051,11
550,750,800,880,961,071,131,19
75700,680,720,780,860,940,991,04
650,720,760,830,911,001,051,11
600,750,800,880,961,071,131,19
550,790,850,931,031,141,211,29
500,840,900,991,101,231,311,39
70650,750,800,880,961,071,131,19
600,790,850,931,031,141,211,29
550,840,900,991,101,231,311,39
500,890,951,051,181,331,421,52
450,941,011,131,271,441,541,66
65600,840,900,991,101,231,311,39
550,890,951,051,181,331,421,52
500,941,011,131,271,441,541,66
451,001,081,211,371,571,691,84
60550,941,011,131,271,441,541,66
501,001,081,211,371,571,691,84
451,071,161,311,491,731,872,04
401,141,251,421,631,912,092,29
55501,071,161,311,491,731,872,04
451,141,251,421,631,912,092,29
401,231,351,541,802,142,352,61
351,331,471,692,002,412,683,01
50451,231,351,541,802,142,352,61
401,331,471,692,002,412,683,01
351,441,601,872,242,763,103,53
301,571,762,092,543,203,664,25
45401,441,601,872,242,763,103,53
351,571,762,092,543,203,664,25
301,731,952,352,923,794,435,27
40351,731,952,352,923,794,435,27
301,912,192,683,424,615,536,84

LEGENDA:
tz – temperatura zasilania
tp – temperatura powrotu

W opisie parametrów grzejnika tz występuje jako pierwsza wartość, tp jako druga, a tempertura pomieszczenia jako trzecia, np. 55/45/20

Aby obliczyć moc grzewczą dla niestandardowych parametrów zasilania należy podzielić moc grzewczą dla parametru 75/65/20 przez wartość odczytaną z tabeli współczynników korekcyjnych.
Np. Szukamy mocy grzewczej dla grzejnika S6/60 dla parametru 70/50/20. Moc dla 75/65/20 wynosi 922 W. W tabeli współczynników korekcyjnych odczytujemy wartość współczynnika dla: tz = 70, tp = 50, temperatura pomieszczenia = 20. Dla tych parametrów współczynnik wynosi: 1,246.
Zatem: 922/1,246 ≈740 W

Współczynniki korekcyjne dla grzejników stojących REGULUS-system VERTAGO

temperatura pomieszczenia
tztp581216202224
95900.5750.5950.6240.6560.6920.7110.731
850.5920.6130.6440.6780.7160.7370.758
800.6090.6320.6650.7010.7420.7640.788
750.6280.6520.6870.7260.7700.7940.819
700.6480.6740.7110.7530.8000.8260.854
90850.6100.6330.6650.7020.7430.7650.788
800.6290.6530.6880.7270.7710.7950.820
750.6490.6740.7120.7540.8010.8270.854
700.6700.6970.7370.7820.8340.8620.892
650.6920.7220.7650.8140.8690.90.933
85800.6490.6750.7120.7540.8020.8280.855
750.6710.6980.7380.7830.8340.8630.893
700.6930.7220.7660.8140.8700.9010.934
650.7170.7490.7950.8480.9090.9420.978
600.7430.7770.8280.8850.9510.9881.028
80750.6940.7230.7670.8150.8710.9020.935
700.7180.7500.7960.8490.9100.9430.980
650.7440.7780.8290.8860.9520.9891.029
600.7720.8090.8640.9260.9991.0401.084
550.8030.8420.9020.9701.0501.0961.145
75700.7450.7790.830.8870.9530.9901.mar
650.7730.8100.8650.9271.0001.0411.085
600.8040.8430.9030.9711.0521.0971.146
550.8360.8790.9441.0201.1091.1591.215
500.8720.9190.9901.0741.1731.2291.292
70650.8050.8440.9040.9731.0531.0981.148
600.8370.8810.9461.0211.1101.1611.216
550.8730.9200.9921.0751.1741.2311.294
500.9120.9641.0421.1351.2461.3101.382
450.9551.0111.0981.2021.3271.4011.483
65600.8740.9210.9931.0771.1761.2331.295
550.9130.9651.0441.1361.2481.3121.383
500.9561.0131.1001.2041.3291.4031.485
60550.9571.0141.1011.2051.3311.4051.487
501.0041.0671.1641.2811.4241.5091.604
451.0561.1261.2341.3671.5321.6301.742
401.1131.1911.3141.4651.6571.7721.906
55501.0581.1271.2361.3691.5341.6331.745
451.1151.1931.3161.4681.6591.7751.909
401.1791.2671.4071.5821.8071.9462.108
351.2521.3511.5111.7151.9842.1532.354
50451.1821.2691.4091.5851.8101.9492.112
401.2541.3531.5141.7181.9872.1572.358
351.3361.4491.6361.8772.2042.4142.670
301.429sty.561.7782.0692.4732.7423.078
45401.3381.4521.6391.8812.2082.4192.675
351.4321.5631.7822.0732.4782.7483.084
301.5401.6931.9532.3082.8243.1813.642
40351.5431.6971.9572.3142.8313.188mar.65
301.6691.8512.1662.6113.2923.7884.462

LEGENDA:
tz – temperatura zasilania
tp – temperatura powrotu

W opisie parametrów grzejnika tz występuje jako pierwsza wartość, tp jako druga, a tempertura pomieszczenia jako trzecia, np. 55/45/20

Aby obliczyć moc grzewczą dla niestandardowych parametrów zasilania należy podzielić moc grzewczą dla parametru 75/65/20 przez wartość odczytaną z tabeli współczynników korekcyjnych.
Np. Szukamy mocy grzewczej dla grzejnika S6/60 dla parametru 70/50/20. Moc dla 75/65/20 wynosi 922 W. W tabeli współczynników korekcyjnych odczytujemy wartość współczynnika dla: tz = 70, tp = 50, temperatura pomieszczenia = 20. Dla tych parametrów współczynnik wynosi: 1,246.
Zatem: 922/1,246 ≈740 W

Współczynniki korekcyjne dla grzejników stojących narożnych REGULUS-system S-CORNER

temperatura pomieszczenia
tztp581216202224
95900.5750.5950.6240.6560.6920.7110.731
850.5920.6130.6440.6780.7160.7370.758
800.6090.6320.6650.7010.7420.7640.788
750.6280.6520.6870.7260.7700.7940.819
700.6480.6740.7110.7530.8000.8260.854
90850.6100.6330.6650.7020.7430.7650.788
800.6290.6530.6880.7270.7710.7950.820
750.6490.6740.7120.7540.8010.8270.854
700.6700.6970.7370.7820.8340.8620.892
650.6920.7220.7650.8140.8690.90.933
85800.6490.6750.7120.7540.8020.8280.855
750.6710.6980.7380.7830.8340.8630.893
700.6930.7220.7660.8140.8700.9010.934
650.7170.7490.7950.8480.9090.9420.978
600.7430.7770.8280.8850.9510.9881.028
80750.6940.7230.7670.8150.8710.9020.935
700.7180.7500.7960.8490.9100.9430.980
650.7440.7780.8290.8860.9520.9891.029
600.7720.8090.8640.9260.9991.0401.084
550.8030.8420.9020.9701.0501.0961.145
75700.7450.7790.830.8870.9530.9901.mar
650.7730.8100.8650.9271.0001.0411.085
600.8040.8430.9030.9711.0521.0971.146
550.8360.8790.9441.0201.1091.1591.215
500.8720.9190.9901.0741.1731.2291.292
70650.8050.8440.9040.9731.0531.0981.148
600.8370.8810.9461.0211.1101.1611.216
550.8730.9200.9921.0751.1741.2311.294
500.9120.9641.0421.1351.2461.3101.382
450.9551.0111.0981.2021.3271.4011.483
65600.8740.9210.9931.0771.1761.2331.295
550.9130.9651.0441.1361.2481.3121.383
500.9561.0131.1001.2041.3291.4031.485
60550.9571.0141.1011.2051.3311.4051.487
501.0041.0671.1641.2811.4241.5091.604
451.0561.1261.2341.3671.5321.6301.742
401.1131.1911.3141.4651.6571.7721.906
55501.0581.1271.2361.3691.5341.6331.745
451.1151.1931.3161.4681.6591.7751.909
401.1791.2671.4071.5821.8071.9462.108
351.2521.3511.5111.7151.9842.1532.354
50451.1821.2691.4091.5851.8101.9492.112
401.2541.3531.5141.7181.9872.1572.358
351.3361.4491.6361.8772.2042.4142.670
301.429sty.561.7782.0692.4732.7423.078
45401.3381.4521.6391.8812.2082.4192.675
351.4321.5631.7822.0732.4782.7483.084
301.5401.6931.9532.3082.8243.1813.642
40351.5431.6971.9572.3142.8313.188mar.65
301.6691.8512.1662.6113.2923.7884.462

LEGENDA:
tz – temperatura zasilania
tp – temperatura powrotu

W opisie parametrów grzejnika tz występuje jako pierwsza wartość, tp jako druga, a tempertura pomieszczenia jako trzecia, np. 55/45/20

Aby obliczyć moc grzewczą dla niestandardowych parametrów zasilania należy podzielić moc grzewczą dla parametru 75/65/20 przez wartość odczytaną z tabeli współczynników korekcyjnych.
Np. Szukamy mocy grzewczej dla grzejnika S6/60 dla parametru 70/50/20. Moc dla 75/65/20 wynosi 922 W. W tabeli współczynników korekcyjnych odczytujemy wartość współczynnika dla: tz = 70, tp = 50, temperatura pomieszczenia = 20. Dla tych parametrów współczynnik wynosi: 1,246.
Zatem: 922/1,246 ≈740 W

Współczynniki korekcyjne dla grzejników kanałowych REGULUS-system CANAL typ SOLO

Temperatura pomieszczenia
tztp581216202224
95900.480.500.530.570.610.630.66
850.500.520.560.600.640.670.69
800.520.540.580.630.680.700.73
750.540.570.610.660.710.740.78
700.570.600.640.700.760.790.83
90850.520.540.580.620.670.700.73
800.540.570.610.650.710.740.77
750.560.590.640.690.750.780.82
700.590.620.670.730.790.830.87
650.620.660.710.770.850.890.93
85800.560.590.630.690.740.780.81
750.590.620.670.720.790.820.86
700.610.650.700.760.830.880.92
650.650.680.740.810.890.940.99
600.680.720.790.870.961.011.07
80750.610.650.700.760.830.870.91
700.640.680.740.800.880.930.97
650.680.720.780.850.940.991.05
600.710.760.830.911.011.071.13
550.760.810.890.981.101.171.24
75700.670.710.780.850.930.981.04
650.710.750.820.901.061.12
600.750.800.880.971.081.141.21
550.790.850.941.041.171.241.33
500.850.911.011.131.281.371.47
70650.740.790.870.961.071.131.20
600.790.840.931.031.151.221.30
550.830.900.991.111.251.331.43
500.890.961.071.211.371.471.59
450.961.041.171.331.531.651.80
65600.830.890.981.101.231.321.41
550.880.951.061.181.341.441.55
500.941.021.141.291.481.591.72
60550.931.011.131.271.461.561.69
501,001.091.221.391.601.741.89
451.081.171.331.531.801.962.15
401.171.281.471.722.052.262.52
55501.071.161.321.511.761.912.09
451.151.261.441.671.972.162.39
401.251.381.591.872.262.512.81
351.371.531.792.152.673.023.47
50451.231.361.561.832.192.422.70
401.341.491.742.062.522.823.19
351.481.661.962.382.993.423.97
301.651.872.262.833.754.465.48
45401.461.621.912.302.863.233.70
351.601.812.162.663.413.944.65
301.802.052.513.194.315.206.50
40351.762,002.423.033.994.695.64
301.972.272.823.665.096.268.03

LEGENDA:
tz – temperatura zasilania
tp – temperatura powrotu

W opisie parametrów grzejnika tz występuje jako pierwsza wartość, tp jako druga, a tempertura pomieszczenia jako trzecia, np. 55/45/20

Aby obliczyć moc grzewczą dla niestandardowych parametrów zasilania należy podzielić moc grzewczą dla parametru 75/65/20 przez wartość odczytaną z tabeli współczynników korekcyjnych.
Np. Szukamy mocy grzewczej dla grzejnika S6/60 dla parametru 70/50/20. Moc dla 75/65/20 wynosi 922 W. W tabeli współczynników korekcyjnych odczytujemy wartość współczynnika dla: tz = 70, tp = 50, temperatura pomieszczenia = 20. Dla tych parametrów współczynnik wynosi: 1,246.
Zatem: 922/1,246 ≈740 W

Współczynniki korekcyjne dla grzejników kanałowych REGULUS-system CANAL typ DUO 100

temperatura pomieszczenia
tztp581216202224
9590 0,440,470,500.540.580.610.63
850.460.490.520.570.610.640.67
800.480.510.550.600.650.680.71
750.510.540.580.630.690.720.76
700.540.570.620.670.740.770.81
90850.480.510.550.590.650.670.71
800.510.530.580.630.680.710.75
750.530.560.610.660.730.760.80
700.560.590.650.710.780.810.86
650.590.630.690.750.830.880.93
85800.530.560.610.660.720.760.79
750.560.590.640.700.770.810.85
700.580.620.680.740.820.860.91
650.620.660.720.790.880.930.99
600.660.700.770.850.951.011.07
80750.580.620.670.740.810.860.90
700.610.650.710.790.870.920.97
650.650.690.760.840.940.991.05
600.690.740.810.911.011.081.15
550.740.790.880.981.111.181.27
75700.650.690.760.830.930.981.04
650.680.730.810.891,001.061.13
600.730.780.860.961.081.161.23
550.780.840.931.051.191.271.36
500.830.901.011.151.311.421.53
70650.720.770.860.951.071.141.22
600.770.830.921.031.171.251.34
550.820.890.991.121.281.371.48
500.880.961.081.231.421.531.66
450.951.041.181.361.591.741.91
65600.810.880.981.111.261.351.45
550.870.941.061.201.381.491.61
500.941.021.161.321.541.671.82
60550.931.011.141.301.511.641.78
501,001.091.251.441.681.832.01
451.081.191.371.601.902.092.32
401.191.321.531.812.202.452.76
55501.071.181.351.571.862.042.25
451.171.291.491.762.112.332.61
401.281.421.671.992.452.753.12
351.421.591.902.322.943.373.93
50451.261.401.641.952.372.642.98
401.381.551.832.222.763.133.58
351.541.742.092.593.333.864.56
301.731.992.453.144.285.176.49
45401.511.702.042.503.173.634.22
351.681.922.332.933.854.525.42
301.902.202.753.584.996.137.84
40351.862.142.643.394.585.476.70
302.112.463.134.175.997.519.89

LEGENDA:
tz – temperatura zasilania
tp – temperatura powrotu

W opisie parametrów grzejnika tz występuje jako pierwsza wartość, tp jako druga, a tempertura pomieszczenia jako trzecia, np. 55/45/20

Aby obliczyć moc grzewczą dla niestandardowych parametrów zasilania należy podzielić moc grzewczą dla parametru 75/65/20 przez wartość odczytaną z tabeli współczynników korekcyjnych.
Np. Szukamy mocy grzewczej dla grzejnika S6/60 dla parametru 70/50/20. Moc dla 75/65/20 wynosi 922 W. W tabeli współczynników korekcyjnych odczytujemy wartość współczynnika dla: tz = 70, tp = 50, temperatura pomieszczenia = 20. Dla tych parametrów współczynnik wynosi: 1,246.
Zatem: 922/1,246 ≈740 W

Współczynniki korekcyjne dla grzejników kanałowych REGULUS-system CANAL typ QUATTRO 150

Temperatura pomieszczenia
tztp581216202224
95900.470.490.530.560.600.630.65
850.490.510.550.590.630.660.69
800.510.540.570.620.670.700.77
750.530.560.600.650.710.740.77
700.560.590.640.690.750.790.82
90850.510.530.570.620.670.690.72
800.530.560.600.650.700.730.76
750.550.580.630.680.740.780.81
700.580.620.660.720.790.830.87
650.610.650.700.770.840.880.93
85800.550.580.630.680.740.770.81
750.580.610.660.720.780.820.86
700.610.640.700.760.830.870.92
650.640.680.740.810.890.930.99
600.680.720.790.860.961.011.07
80750.600.640.690.750.830.870.91
700.630.670.730.800.880.920.97
650.670.710.780.850.940.991.05
600.710.750.830.911.011.071.14
550.750.800.880.981.101.171.25
75700.670.710.770.840.930.981.04
650.700.750.820.901.061.12
600.740.790.870.971.081.141.22
550.790.850.931.041.171.251.33
500.840.911.011.131.291.381.48
70650.740.790.870.961.071.131.20
600.780.840.921.031.151.221.31
550.830.890.991.111.251.341.44
500.890.961.071.211.381.481.60
450.961.041.171.331.541.671.82
65600.830.890.981.101.241.321.41
550.880.951.061.191.351.451.56
500.941.021.141.301.491.611.74
60550.931.011.131.281.471.581.71
501,001.091.221.401.621.751.91
451.081.181.341.551.821.982.18
401.171.291.481.742.082.302.57
55501.071.161.321.521.781.942.12
451.151.261.451.682,002.202.43
401.251.391.611.902.302.552.87
351.381.541.812.182.723.093.56
50451.241.371.581.852.222.462.75
401.351.501.752.092.572.883.27
351.491.671.982.423.063.504.08
301.671.892.302.903.854.605.68
45401.471.641.942.342.923.313.80
351.621.832.202.713.504.064.80
301.822.082.553.274.445.376.76
40351.782.022.463.104.104.845.84
302,002.312.883.765.266.508.38

 

Współczynniki korekcyjne dla grzejników kanałowych REGULUS-system CANAL typ QUATTRO 200/270

Temperatura pomieszczenia#colspan#
tztp581216202224
95900.460.480.510.550.590.620.64
850.480.500.540.580.620.650.69
800.500.520.560.610.660.690.72
750.520.550.590.640.700.730.76
700.550.580.630.680.740.780.82
90850.500.520.560.600.660.680.71
800.520.550.590.640.690.720.76
750.540.570.620.670.730.770.81
700.570.600.650.710.780.820.86
650.600.640.690.760.840.880.93
85800.540.570.620.670.730.760.80
750.570.600.650.710.770.810.85
700.600.630.690.750.830.870.91
650.630.670.730.800.880.930.99
600.670.710.780.860.951.011.07
80750.590.630.680.750.820.860.91
700.620.660.720.790.870.920.97
650.660.700.770.850.940.991.05
600.700.750.820.911.011.071.14
550.740.800.880.981.101.181.26
75700.660.700.760.840.930.981.04
650.690.740.810.901.061.12
600.730.790.870.961.081.151.22
550.780.840.931.041.181.261.35
500.840.901.011.141.301.401.51
70650.730.780.860.961.071.141.21
600.770.830.921.031.161.231.32
550.830.890.991.111.261.351.46
500.880.961.071.221.401.511.63
450.951.041.181.351.571.701.86
65600.820.880.981.101.251.341.43
550.870.951.061.201.371.471.58
450.941.021.151.311.511.641.78
60550.931.011.141.291.491.601.74
501.001.091.231.421.641.791.96
451.081.191.351.571.862.042.25
401.181.301.511.772.142.372.66
55501.071.171.341.541.821.982.18
451.161.281.471.722.052.262.51
401.261.401.641.942.372.642.98
351.401.571.852.252.823.223.73
50451.251.381.601.902.292.552.86
401.371.521.792.152.662.993.41
351.511.702.042.503.193.674.30
301.701.942.373.014.054.866.05
45401.491.671.982.413.043.464.00
351.651.872.262.823.664.275.08
301.862.142.643.414.705.727.25
40351.822.0792.553.244.325.136.24
302.052.382.993.955.606.969.07

LEGENDA:
tz – temperatura zasilania
tp – temperatura powrotu

W opisie parametrów grzejnika tz występuje jako pierwsza wartość, tp jako druga, a tempertura pomieszczenia jako trzecia, np. 55/45/20

Aby obliczyć moc grzewczą dla niestandardowych parametrów zasilania należy podzielić moc grzewczą dla parametru 75/65/20 przez wartość odczytaną z tabeli współczynników korekcyjnych.
Np. Szukamy mocy grzewczej dla grzejnika S6/60 dla parametru 70/50/20. Moc dla 75/65/20 wynosi 922 W. W tabeli współczynników korekcyjnych odczytujemy wartość współczynnika dla: tz = 70, tp = 50, temperatura pomieszczenia = 20. Dla tych parametrów współczynnik wynosi: 1,246.
Zatem: 922/1,246 ≈740 W

Współczynniki korekcyjne dla grzejników kanałowych REGULUS-system CANAL typ TRIOVENT

temperatura pomieszczenia
tztp581216202224
95900,530,550,580,620,660,680,70
850,550,570,600,640,680,710,73
800,570,590,630,670,710,740,76
750,590,610,650,690,740,770,80
700,610,640,680,720,780,810,84
90850,570,590,630,670,710,740,76
800,590,610,650,690,740,770,80
750,610,640,680,720,780,810,84
700,630,660,710,760,810,840,88
650,660,690,740,790,850,890,93
85800,610,640,680,720,780,810,84
750,630,660,710,760,810,840,88
700,660,690,740,790,850,890,93
650,680,720,770,830,900,940,98
600,710,750,810,870,950,991,03
80750,660,690,740,790,850,890,93
700,680,720,770,830,900,940,98
650,710,750,810,870,950,991,03
600,740,780,840,921,001,051,10
550,780,820,890,971,061,111,17
75700,710,750,810,870,950,991,03
650,740,780,840,921,001,051,10
600,780,820,890,971,061,111,17
550,810,860,941,021,131,191,25
500,850,910,991,091,201,271,34
70650,780,820,890,971,061,111,17
600,810,860,941,021,131,191,25
550,850,910,991,091,201,271,34
500,900,961,051,161,291,361,45
450,951,011,111,241,391,471,57
65600,850,910,991,091,201,271,34
550,900,961,051,161,291,361,45
500,951,011,111,241,391,471,57
451,001,071,191,331,501,601,72
60550,951,011,111,241,391,471,57
501,001,071,191,331,501,601,72
451,061,141,271,431,631,751,89
401,131,221,361,551,781,932,10
55501,061,141,271,431,631,751,89
451,131,221,361,551,781,932,10
401,201,311,471,691,972,152,35
351,291,411,601,852,192,412,67
50451,201,311,471,691,972,152,35
401,291,411,601,852,192,412,67
351,391,521,752,052,472,753,09
301,501,661,932,302,833,193,64
45401,391,521,752,052,472,753,09
351,501,661,932,302,833,193,64
301,631,822,152,603,293,774,42
40351,631,822,152,603,293,774,42
301,782,012,413,003,924,615,57

LEGENDA:
tz – temperatura zasilania
tp – temperatura powrotu

W opisie parametrów grzejnika tz występuje jako pierwsza wartość, tp jako druga, a tempertura pomieszczenia jako trzecia, np. 55/45/20

Aby obliczyć moc grzewczą dla niestandardowych parametrów zasilania należy podzielić moc grzewczą dla parametru 75/65/20 przez wartość odczytaną z tabeli współczynników korekcyjnych.
Np. Szukamy mocy grzewczej dla grzejnika S6/60 dla parametru 70/50/20. Moc dla 75/65/20 wynosi 922 W. W tabeli współczynników korekcyjnych odczytujemy wartość współczynnika dla: tz = 70, tp = 50, temperatura pomieszczenia = 20. Dla tych parametrów współczynnik wynosi: 1,246.
Zatem: 922/1,246 ≈740 W

Współczynniki korekcyjne dla grzejników kanałowych REGULUS-system CANAL typ QUATTROVENT

temperatura pomieszczenia
tztp581216202224
95900,560,580,610,640,680,700,72
850,570,600,630,660,700,720,75
800,590,620,650,690,730,750,78
750,610,640,670,710,760,790,81
700,630,660,700,740,790,820,85
90850,590,620,650,690,730,750,78
800,610,640,670,710,760,790,81
750,630,660,700,740,790,820,85
700,650,680,720,770,830,860,89
650,680,710,750,810,860,900,93
85800,630,660,700,740,790,820,85
750,650,680,720,770,830,860,89
700,680,710,750,810,860,900,93
650,700,740,790,840,910,940,98
600,730,770,820,880,950,991,03
80750,680,710,750,810,860,900,93
700,700,740,790,840,910,940,98
650,730,770,820,880,950,991,03
600,760,800,860,921,001,041,09
550,790,830,900,971,061,101,16
75700,730,770,820,880,950,991,03
650,760,800,860,921,001,041,09
600,790,830,900,971,061,101,16
550,830,870,941,021,121,171,23
500,860,910,991,081,191,251,31
70650,790,830,900,971,061,101,16
600,830,870,941,021,121,171,23
550,860,910,991,081,191,251,31
500,910,961,041,141,261,331,41
450,951,011,101,221,351,431,52
65600,860,910,991,081,191,251,31
550,910,961,041,141,261,331,41
500,951,011,101,221,351,431,52
451,001,071,171,301,451,551,65
60550,951,011,101,221,351,431,52
501,001,071,171,301,451,551,65
451,061,131,251,391,571,681,80
401,121,201,331,501,711,841,98
55501,061,131,251,391,571,681,80
451,121,201,331,501,711,841,98
401,191,281,431,621,872,022,20
351,261,371,551,772,072,252,48
50451,191,281,431,621,872,022,20
401,261,371,551,772,072,252,48
351,351,471,681,942,312,542,83
301,451,601,842,162,612,913,30
45401,351,471,681,942,312,542,83
351,451,601,842,162,612,913,30
301,571,742,022,423,003,413,94
40351,571,742,022,423,003,413,94
301,711,912,252,753,534,104,88

LEGENDA:
tz – temperatura zasilania
tp – temperatura powrotu

W opisie parametrów grzejnika tz występuje jako pierwsza wartość, tp jako druga, a tempertura pomieszczenia jako trzecia, np. 55/45/20

Aby obliczyć moc grzewczą dla niestandardowych parametrów zasilania należy podzielić moc grzewczą dla parametru 75/65/20 przez wartość odczytaną z tabeli współczynników korekcyjnych.
Np. Szukamy mocy grzewczej dla grzejnika S6/60 dla parametru 70/50/20. Moc dla 75/65/20 wynosi 922 W. W tabeli współczynników korekcyjnych odczytujemy wartość współczynnika dla: tz = 70, tp = 50, temperatura pomieszczenia = 20. Dla tych parametrów współczynnik wynosi: 1,246.
Zatem: 922/1,246 ≈740 W

Współczynniki korekcyjne dla grzejników ściennych REGULUS-system REGULLUS

tztp581216202224
95900,550,570,600,630,670,690,71
850,570,590,620,660,700,720,74
800,580,610,640,680,720,750,77
750,600,630,670,710,750,780,81
700,620,650,690,740,790,810,84
90850,580,610,640,680,720,750,77
800,600,630,670,710,750,780,81
750,620,650,690,740,790,810,84
700,650,680,720,770,820,850,89
650,670,700,750,800,860,890,93
85800,620,650,690,740,790,810,84
750,650,680,720,770,820,850,89
700,670,700,750,800,860,890,93
650,700,730,780,840,900,940,98
600,720,760,810,880,950,991,03
80750,670,700,750,800,860,890,93
700,700,730,780,840,900,940,98
650,720,760,810,880,950,991,03
600,750,790,850,921,001,051,09
550,790,830,890,971,061,111,16
75700,720,760,810,880,950,991,03
650,750,790,850,921,001,051,09
600,790,830,890,971,061,111,16
550,820,870,941,021,121,181,24
500,860,910,991,081,191,251,33
70650,790,830,890,971,061,111,16
600,820,870,941,021,121,181,24
550,860,910,991,081,191,251,33
500,900,961,051,151,271,341,42
450,951,011,111,221,361,451,54
65600,860,910,991,081,191,251,33
550,900,961,051,151,271,341,42
500,951,011,111,221,361,451,54
451,001,071,181,311,471,561,67
60550,951,011,111,221,361,451,54
501,001,071,181,311,471,561,67
451,061,131,251,401,591,701,83
401,121,211,341,511,731,872,02
55501,061,131,251,401,591,701,83
451,121,211,341,511,731,872,02
401,191,291,451,641,902,062,25
351,271,381,561,802,112,312,54
50451,191,291,451,641,902,062,25
401,271,381,561,802,112,312,54
351,361,491,701,982,362,612,92
301,471,621,872,202,683,003,41
45401,361,491,701,982,362,612,92
351,471,621,872,202,683,003,41
301,591,762,062,483,103,534,09
40351,591,762,062,483,103,534,09
301,731,942,312,833,654,265,10

LEGENDA:
tz – temperatura zasilania
tp – temperatura powrotu

W opisie parametrów grzejnika tz występuje jako pierwsza wartość, tp jako druga, a tempertura pomieszczenia jako trzecia, np. 55/45/20

Aby obliczyć moc grzewczą dla niestandardowych parametrów zasilania należy podzielić moc grzewczą dla parametru 75/65/20 przez wartość odczytaną z tabeli współczynników korekcyjnych.
Np. Szukamy mocy grzewczej dla grzejnika S6/60 dla parametru 70/50/20. Moc dla 75/65/20 wynosi 922 W. W tabeli współczynników korekcyjnych odczytujemy wartość współczynnika dla: tz = 70, tp = 50, temperatura pomieszczenia = 20. Dla tych parametrów współczynnik wynosi: 1,246.
Zatem: 922/1,246 ≈740 W

Współczynniki korekcyjne dla grzejników ściennych REGULUS-system REGULLUS

temperatura pomieszczenia
tztp581216202224
95900,550,570,600,640,670,690,72
850,570,590,620,660,700,720,74
800,590,610,650,680,730,750,78
750,610,630,670,710,760,780,81
700,630,650,690,740,790,820,85
90850,590,610,650,680,730,750,78
800,610,630,670,710,760,780,81
750,630,650,690,740,790,820,85
700,650,680,720,770,820,850,89
650,670,700,750,800,860,900,93
85800,630,650,690,740,790,820,85
750,650,680,720,770,820,850,89
700,670,700,750,800,860,900,93
650,700,730,780,840,900,940,98
600,730,760,820,880,950,991,03
80750,670,700,750,800,860,900,93
700,700,730,780,840,900,940,98
650,730,760,820,880,950,991,03
600,760,800,850,921,001,041,09
550,790,830,900,971,061,111,16
75700,730,760,820,880,950,991,03
650,760,800,850,921,0001,041,09
600,790,830,900,971,061,111,16
550,820,870,941,021,121,171,23
500,860,910,991,081,191,251,32
70650,790,830,900,971,061,111,16
600,820,870,941,021,121,171,23
550,860,910,991,081,191,251,32
500,900,961,041,151,271,341,42
450,951,011,111,221,361,441,53
65600,860,910,991,081,191,251,32
550,900,961,041,151,271,341,42
500,951,011,111,221,361,441,53
451,001,071,171,301,461,561,66
60550,951,011,111,221,361,441,53
501,001,071,171,301,461,561,66
451,061,131,251,401,581,691,82
401,121,201,341,511,721,852,00
55501,061,131,251,401,581,691,82
451,121,201,341,511,721,852,00
401,191,281,441,631,892,052,23
351,271,381,561,782,092,282,51
50451,191,281,441,631,892,052,23
401,271,381,561,782,092,282,51
351,361,481,691,962,342,582,88
301,461,611,852,182,652,963,36
45401,361,481,691,962,342,582,88
351,461,611,852,182,652,963,36
301,581,752,052,453,053,474,02
40351,581,752,052,453,053,474,02
301,721,922,282,803,594,185,00

LEGENDA:
tz – temperatura zasilania
tp – temperatura powrotu

W opisie parametrów grzejnika tz występuje jako pierwsza wartość, tp jako druga, a tempertura pomieszczenia jako trzecia, np. 55/45/20

Aby obliczyć moc grzewczą dla niestandardowych parametrów zasilania należy podzielić moc grzewczą dla parametru 75/65/20 przez wartość odczytaną z tabeli współczynników korekcyjnych.
Np. Szukamy mocy grzewczej dla grzejnika S6/60 dla parametru 70/50/20. Moc dla 75/65/20 wynosi 922 W. W tabeli współczynników korekcyjnych odczytujemy wartość współczynnika dla: tz = 70, tp = 50, temperatura pomieszczenia = 20. Dla tych parametrów współczynnik wynosi: 1,246.
Zatem: 922/1,246 ≈740 W

Współczynniki korekcyjne dla grzejników ściennych REGULUS-system REGULLUS

temperatura pomieszczenia
tztp581216202224
95900,570,590,620,650,690,710,73
850,590,610,640,670,710,730,76
800,600,630,660,700,740,760,79
750,620,650,680,720,770,790,82
700,640,670,710,750,800,830,85
90850,600,630,660,700,740,760,79
800,620,650,680,720,770,790,82
750,640,670,710,750,800,830,85
700,670,690,730,780,830,860,89
650,690,720,760,810,870,900,93
85800,640,670,710,750,800,830,85
750,670,690,730,780,830,860,89
700,690,720,760,810,870,900,93
650,710,750,790,850,910,940,98
600,740,770,830,880,950,991,03
80750,690,720,760,810,870,900,93
700,710,750,790,850,910,940,98
650,740,770,830,880,950,991,03
600,770,810,860,931,001,041,09
550,800,840,900,971,051,101,15
75700,740,770,830,880,950,991,03
650,770,810,860,931,0001,041,09
600,800,840,900,971,051,101,15
550,830,880,941,021,111,161,22
500,870,920,991,081,181,241,30
70650,800,840,900,971,051,101,15
600,830,880,941,021,111,161,22
550,870,920,991,081,181,241,30
500,910,961,041,141,251,321,39
450,951,011,101,211,341,411,50
65600,870,920,991,081,181,241,30
550,910,961,041,141,251,321,39
500,951,011,101,211,341,411,50
451,001,061,161,281,431,521,62
60550,951,011,101,211,341,411,50
501,001,061,161,281,431,521,62
451,051,121,241,371,541,641,76
401,111,191,321,471,671,791,93
55501,051,121,241,371,541,641,76
451,111,191,321,471,671,791,93
401,181,271,411,591,821,972,14
351,251,351,521,732,012,182,39
50451,181,271,411,591,821,972,14
401,251,351,521,732,012,182,39
351,341,451,641,892,232,452,72
301,431,571,792,092,512,803,15
45401,341,451,641,892,232,452,72
351,431,571,792,092,512,803,15
301,541,701,972,342,883,253,73
40351,541,701,972,342,883,253,73
301,671,862,182,653,363,884,59

LEGENDA:
tz – temperatura zasilania
tp – temperatura powrotu

W opisie parametrów grzejnika tz występuje jako pierwsza wartość, tp jako druga, a tempertura pomieszczenia jako trzecia, np. 55/45/20

Aby obliczyć moc grzewczą dla niestandardowych parametrów zasilania należy podzielić moc grzewczą dla parametru 75/65/20 przez wartość odczytaną z tabeli współczynników korekcyjnych.
Np. Szukamy mocy grzewczej dla grzejnika S6/60 dla parametru 70/50/20. Moc dla 75/65/20 wynosi 922 W. W tabeli współczynników korekcyjnych odczytujemy wartość współczynnika dla: tz = 70, tp = 50, temperatura pomieszczenia = 20. Dla tych parametrów współczynnik wynosi: 1,246.
Zatem: 922/1,246 ≈740 W

REGULLUS

Współczynniki korekcyjne dla grzejników ściennych REGULUS-system REGULLUS

temperatura pomieszczenia
tztp581216202224
95900.5750.5950.6240.6560.6920.7110.731
850.5920.6130.6440.6780.7160.7370.758
800.6090.6320.6650.7010.7420.7640.788
750.6280.6520.6870.7260.7700.7940.819
700.6480.6740.7110.7530.8000.8260.854
90850.6100.6330.6650.7020.7430.7650.788
800.6290.6530.6880.7270.7710.7950.820
750.6490.6740.7120.7540.8010.8270.854
700.6700.6970.7370.7820.8340.8620.892
650.6920.7220.7650.8140.8690.90.933
85800.6490.6750.7120.7540.8020.8280.855
750.6710.6980.7380.7830.8340.8630.893
700.6930.7220.7660.8140.8700.9010.934
650.7170.7490.7950.8480.9090.9420.978
600.7430.7770.8280.8850.9510.9881.028
80750.6940.7230.7670.8150.8710.9020.935
700.7180.7500.7960.8490.9100.9430.980
650.7440.7780.8290.8860.9520.9891.029
600.7720.8090.8640.9260.9991.0401.084
550.8030.8420.9020.9701.0501.0961.145
75700.7450.7790.830.8870.9530.9901.mar
650.7730.8100.8650.9271.0001.0411.085
600.8040.8430.9030.9711.0521.0971.146
550.8360.8790.9441.0201.1091.1591.215
500.8720.9190.9901.0741.1731.2291.292
70650.8050.8440.9040.9731.0531.0981.148
600.8370.8810.9461.0211.1101.1611.216
550.8730.9200.9921.0751.1741.2311.294
500.9120.9641.0421.1351.2461.3101.382
450.9551.0111.0981.2021.3271.4011.483
65600.8740.9210.9931.0771.1761.2331.295
550.9130.9651.0441.1361.2481.3121.383
500.9561.0131.1001.2041.3291.4031.485
60550.9571.0141.1011.2051.3311.4051.487
501.0041.0671.1641.2811.4241.5091.604
451.0561.1261.2341.3671.5321.6301.742
401.1131.1911.3141.4651.6571.7721.906
55501.0581.1271.2361.3691.5341.6331.745
451.1151.1931.3161.4681.6591.7751.909
401.1791.2671.4071.5821.8071.9462.108
351.2521.3511.5111.7151.9842.1532.354
50451.1821.2691.4091.5851.8101.9492.112
401.2541.3531.5141.7181.9872.1572.358
351.3361.4491.6361.8772.2042.4142.670
301.429sty.561.7782.0692.4732.7423.078
45401.3381.4521.6391.8812.2082.4192.675
351.4321.5631.7822.0732.4782.7483.084
301.5401.6931.9532.3082.8243.1813.642
40351.5431.6971.9572.3142.8313.188mar.65
301.6691.8512.1662.6113.2923.7884.462

LEGENDA:
tz – temperatura zasilania
tp – temperatura powrotu

W opisie parametrów grzejnika tz występuje jako pierwsza wartość, tp jako druga, a tempertura pomieszczenia jako trzecia, np. 55/45/20

Aby obliczyć moc grzewczą dla niestandardowych parametrów zasilania należy podzielić moc grzewczą dla parametru 75/65/20 przez wartość odczytaną z tabeli współczynników korekcyjnych.
Np. Szukamy mocy grzewczej dla grzejnika S6/60 dla parametru 70/50/20. Moc dla 75/65/20 wynosi 922 W. W tabeli współczynników korekcyjnych odczytujemy wartość współczynnika dla: tz = 70, tp = 50, temperatura pomieszczenia = 20. Dla tych parametrów współczynnik wynosi: 1,246.
Zatem: 922/1,246 ≈740 W

SOLLARIUS

Współczynniki korekcyjne dla grzejników ściennych REGULUS-system SOLLARIUS

temperatura pomieszczenia
tztp581216202224
95900.5750.5950.6240.6560.6920.7110.731
850.5920.6130.6440.6780.7160.7370.758
800.6090.6320.6650.7010.7420.7640.788
750.6280.6520.6870.7260.7700.7940.819
700.6480.6740.7110.7530.8000.8260.854
90850.6100.6330.6650.7020.7430.7650.788
800.6290.6530.6880.7270.7710.7950.820
750.6490.6740.7120.7540.8010.8270.854
700.6700.6970.7370.7820.8340.8620.892
650.6920.7220.7650.8140.8690.90.933
85800.6490.6750.7120.7540.8020.8280.855
750.6710.6980.7380.7830.8340.8630.893
700.6930.7220.7660.8140.8700.9010.934
650.7170.7490.7950.8480.9090.9420.978
600.7430.7770.8280.8850.9510.9881.028
80750.6940.7230.7670.8150.8710.9020.935
700.7180.7500.7960.8490.9100.9430.980
650.7440.7780.8290.8860.9520.9891.029
600.7720.8090.8640.9260.9991.0401.084
550.8030.8420.9020.9701.0501.0961.145
75700.7450.7790.830.8870.9530.9901.mar
650.7730.8100.8650.9271.0001.0411.085
600.8040.8430.9030.9711.0521.0971.146
550.8360.8790.9441.0201.1091.1591.215
500.8720.9190.9901.0741.1731.2291.292
70650.8050.8440.9040.9731.0531.0981.148
600.8370.8810.9461.0211.1101.1611.216
550.8730.9200.9921.0751.1741.2311.294
500.9120.9641.0421.1351.2461.3101.382
450.9551.0111.0981.2021.3271.4011.483
65600.8740.9210.9931.0771.1761.2331.295
550.9130.9651.0441.1361.2481.3121.383
500.9561.0131.1001.2041.3291.4031.485
60550.9571.0141.1011.2051.3311.4051.487
501.0041.0671.1641.2811.4241.5091.604
451.0561.1261.2341.3671.5321.6301.742
401.1131.1911.3141.4651.6571.7721.906
55501.0581.1271.2361.3691.5341.6331.745
451.1151.1931.3161.4681.6591.7751.909
401.1791.2671.4071.5821.8071.9462.108
351.2521.3511.5111.7151.9842.1532.354
50451.1821.2691.4091.5851.8101.9492.112
401.2541.3531.5141.7181.9872.1572.358
351.3361.4491.6361.8772.2042.4142.670
301.429sty.561.7782.0692.4732.7423.078
45401.3381.4521.6391.8812.2082.4192.675
351.4321.5631.7822.0732.4782.7483.084
301.5401.6931.9532.3082.8243.1813.642
40351.5431.6971.9572.3142.8313.188mar.65
301.6691.8512.1662.6113.2923.7884.462

LEGENDA:
tz – temperatura zasilania
tp – temperatura powrotu

W opisie parametrów grzejnika tz występuje jako pierwsza wartość, tp jako druga, a tempertura pomieszczenia jako trzecia, np. 55/45/20

Aby obliczyć moc grzewczą dla niestandardowych parametrów zasilania należy podzielić moc grzewczą dla parametru 75/65/20 przez wartość odczytaną z tabeli współczynników korekcyjnych.
Np. Szukamy mocy grzewczej dla grzejnika S6/60 dla parametru 70/50/20. Moc dla 75/65/20 wynosi 922 W. W tabeli współczynników korekcyjnych odczytujemy wartość współczynnika dla: tz = 70, tp = 50, temperatura pomieszczenia = 20. Dla tych parametrów współczynnik wynosi: 1,246.
Zatem: 922/1,246 ≈740 W

DUBEL

Współczynniki korekcyjne dla grzejników ściennych REGULUS-system DUBEL

temperatura pomieszczenia
tztp581216202224
95900.5750.5950.6240.6560.6920.7110.731
850.5920.6130.6440.6780.7160.7370.758
800.6090.6320.6650.7010.7420.7640.788
750.6280.6520.6870.7260.7700.7940.819
700.6480.6740.7110.7530.8000.8260.854
90850.6100.6330.6650.7020.7430.7650.788
800.6290.6530.6880.7270.7710.7950.820
750.6490.6740.7120.7540.8010.8270.854
700.6700.6970.7370.7820.8340.8620.892
650.6920.7220.7650.8140.8690.90.933
85800.6490.6750.7120.7540.8020.8280.855
750.6710.6980.7380.7830.8340.8630.893
700.6930.7220.7660.8140.8700.9010.934
650.7170.7490.7950.8480.9090.9420.978
600.7430.7770.8280.8850.9510.9881.028
80750.6940.7230.7670.8150.8710.9020.935
700.7180.7500.7960.8490.9100.9430.980
650.7440.7780.8290.8860.9520.9891.029
600.7720.8090.8640.9260.9991.0401.084
550.8030.8420.9020.9701.0501.0961.145
75700.7450.7790.830.8870.9530.9901.mar
650.7730.8100.8650.9271.0001.0411.085
600.8040.8430.9030.9711.0521.0971.146
550.8360.8790.9441.0201.1091.1591.215
500.8720.9190.9901.0741.1731.2291.292
70650.8050.8440.9040.9731.0531.0981.148
600.8370.8810.9461.0211.1101.1611.216
550.8730.9200.9921.0751.1741.2311.294
500.9120.9641.0421.1351.2461.3101.382
450.9551.0111.0981.2021.3271.4011.483
65600.8740.9210.9931.0771.1761.2331.295
550.9130.9651.0441.1361.2481.3121.383
500.9561.0131.1001.2041.3291.4031.485
60550.9571.0141.1011.2051.3311.4051.487
501.0041.0671.1641.2811.4241.5091.604
451.0561.1261.2341.3671.5321.6301.742
401.1131.1911.3141.4651.6571.7721.906
55501.0581.1271.2361.3691.5341.6331.745
451.1151.1931.3161.4681.6591.7751.909
401.1791.2671.4071.5821.8071.9462.108
351.2521.3511.5111.7151.9842.1532.354
50451.1821.2691.4091.5851.8101.9492.112
401.2541.3531.5141.7181.9872.1572.358
351.3361.4491.6361.8772.2042.4142.670
301.429sty.561.7782.0692.4732.7423.078
45401.3381.4521.6391.8812.2082.4192.675
351.4321.5631.7822.0732.4782.7483.084
301.5401.6931.9532.3082.8243.1813.642
40351.5431.6971.9572.3142.8313.188mar.65
301.6691.8512.1662.6113.2923.7884.462

LEGENDA:
tz – temperatura zasilania
tp – temperatura powrotu

W opisie parametrów grzejnika tz występuje jako pierwsza wartość, tp jako druga, a tempertura pomieszczenia jako trzecia, np. 55/45/20

Aby obliczyć moc grzewczą dla niestandardowych parametrów zasilania należy podzielić moc grzewczą dla parametru 75/65/20 przez wartość odczytaną z tabeli współczynników korekcyjnych.
Np. Szukamy mocy grzewczej dla grzejnika S6/60 dla parametru 70/50/20. Moc dla 75/65/20 wynosi 922 W. W tabeli współczynników korekcyjnych odczytujemy wartość współczynnika dla: tz = 70, tp = 50, temperatura pomieszczenia = 20. Dla tych parametrów współczynnik wynosi: 1,246.
Zatem: 922/1,246 ≈740 W

E-VENT

Współczynniki korekcyjne dla grzejników ściennych REGULUS-system E-VENT

Temperatura pomieszczenia
tztp581216202224
95900.5830.6030.6320.6630.6990.7180.738
850.5990.6200.6510.6850.7230.7430.765
800.6170.6390.6720.7080.7480.7700.794
750.6350.6590.6940.7330.7760.8060.825
700.6550.6810.7180.7590.8060.8320.859
90850.6170.6390.6720.7080.7480.7700.794
800.6350.6590.6940.7330.7760.8060.825
750.6550.6810.7180.7590.8060.8320.859
700.6760.7030.7430.7880.8390.8660.896
650.6990.7280.7700.8190.8740.9040.937
85800.6550.6810.7180.7590.8060.8320.859
750.6760.7030.7430.7880.8660.896
700.6990.7280.7700.8190.8740.9040.937
650.7230.7540.8000.8520.9120.9450.981
600.7480.7820.8320.8890.9540.9901.030
80750.6990.7280.7700.8190.8740.9040.937
700.7230.7540.8000.8520.9120.9450.981
650.7480.7820.8320.8890.9540.9901.030
600.7760.8120.8660.9281.0001.0401.083
550.8060.8450.9040.9721.0501.0951.143
75700.7480.7820.8320.8890.9540.9901.030
650.7760.8120.8660.9281.0401.083
600.8060.8450.9040.9721.0501.0951.143
550.8390.8810.9451.0191.1071.1561.211
500.8740.9200.9901.0721.1691.2251.286
70650.8060.8450.9040.9721.0501.0951.143
600.8390.8810.9451.0191.1071.1561.211
550.8740.9200.9901.0721.1691.2251.286
500.9120.9631.0401.1311.2401.3031.373
450.9541.0091.0951.1971.3201.3911.471
65600.8740.9200.9901.0721.1691.2251.286
550.9120.9631.0401.1311.2401.3031.373
500.9541.0091.0951.1971.3201.3911.471
60550.9541.0091.0951.1971.3201.3911.471
501.0001.0611.1561.2711.4101.4931.585
451.0501.1191.2251.3541.5151.6111.719
401.1071.1831.3031.4501.6361.7491.879
55501.0501.1191.2251.3541.5151.6111.719
451.1071.1831.3031.4501.7491.879
401.1691.2551.3911.5611.7801.9142.071
351.2401.3371.4931.6911.9512.1152.308
50451.1691.2551.3911.5611.7801.9142.071
401.2401.3371.4931.6911.9512.1152.308
351.3201.4301.6111.8442.1602.3632.609
301.4101.5381.7492.0292.4202.6793.001
45401.3201.431.6111.8442.1602.3632.609
351.4101.5381.7492.0292.4202.6793.001
301.5151.6631.9142.2572.7523.0943.535
40351.5151.6631.9142.2572.7523.0943.535
301.6361.8112.1152.5423.1943.6664.307

LEGENDA:
tz – temperatura zasilania
tp – temperatura powrotu

W opisie parametrów grzejnika tz występuje jako pierwsza wartość, tp jako druga, a tempertura pomieszczenia jako trzecia, np. 55/45/20

Aby obliczyć moc grzewczą dla niestandardowych parametrów zasilania należy podzielić moc grzewczą dla parametru 75/65/20 przez wartość odczytaną z tabeli współczynników korekcyjnych.
Np. Szukamy mocy grzewczej dla grzejnika S6/60 dla parametru 70/50/20. Moc dla 75/65/20 wynosi 922 W. W tabeli współczynników korekcyjnych odczytujemy wartość współczynnika dla: tz = 70, tp = 50, temperatura pomieszczenia = 20. Dla tych parametrów współczynnik wynosi: 1,246.
Zatem: 922/1,246 ≈740 W

REVERS

Współczynniki korekcyjne dla grzejników ściennych REGULUS-system REVERS

Temperatura pomieszczenia
tztp581216202224
95900.5830.6030.6320.6630.6990.7180.738
850.5990.6200.6510.6850.7230.7430.765
800.6170.6390.6720.7080.7480.7700.794
750.6350.6590.6940.7330.7760.8060.825
700.6550.6810.7180.7590.8060.8320.859
90850.6170.6390.6720.7080.7480.7700.794
800.6350.6590.6940.7330.7760.8060.825
750.6550.6810.7180.7590.8060.8320.859
700.6760.7030.7430.7880.8390.8660.896
650.6990.7280.7700.8190.8740.9040.937
85800.6550.6810.7180.7590.8060.8320.859
750.6760.7030.7430.7880.8660.896
700.6990.7280.7700.8190.8740.9040.937
650.7230.7540.8000.8520.9120.9450.981
600.7480.7820.8320.8890.9540.9901.030
80750.6990.7280.7700.8190.8740.9040.937
700.7230.7540.8000.8520.9120.9450.981
650.7480.7820.8320.8890.9540.9901.030
600.7760.8120.8660.9281.0001.0401.083
550.8060.8450.9040.9721.0501.0951.143
75700.7480.7820.8320.8890.9540.9901.030
650.7760.8120.8660.9281.0401.083
600.8060.8450.9040.9721.0501.0951.143
550.8390.8810.9451.0191.1071.1561.211
500.8740.9200.9901.0721.1691.2251.286
70650.8060.8450.9040.9721.0501.0951.143
600.8390.8810.9451.0191.1071.1561.211
550.8740.9200.9901.0721.1691.2251.286
500.9120.9631.0401.1311.2401.3031.373
450.9541.0091.0951.1971.3201.3911.471
65600.8740.9200.9901.0721.1691.2251.286
550.9120.9631.0401.1311.2401.3031.373
500.9541.0091.0951.1971.3201.3911.471
60550.9541.0091.0951.1971.3201.3911.471
501.0001.0611.1561.2711.4101.4931.585
451.0501.1191.2251.3541.5151.6111.719
401.1071.1831.3031.4501.6361.7491.879
55501.0501.1191.2251.3541.5151.6111.719
451.1071.1831.3031.4501.7491.879
401.1691.2551.3911.5611.7801.9142.071
351.2401.3371.4931.6911.9512.1152.308
50451.1691.2551.3911.5611.7801.9142.071
401.2401.3371.4931.6911.9512.1152.308
351.3201.4301.6111.8442.1602.3632.609
301.4101.5381.7492.0292.4202.6793.001
45401.3201.431.6111.8442.1602.3632.609
351.4101.5381.7492.0292.4202.6793.001
301.5151.6631.9142.2572.7523.0943.535
40351.5151.6631.9142.2572.7523.0943.535
301.6361.8112.1152.5423.1943.6664.307

LEGENDA:
tz – temperatura zasilania
tp – temperatura powrotu

W opisie parametrów grzejnika tz występuje jako pierwsza wartość, tp jako druga, a tempertura pomieszczenia jako trzecia, np. 55/45/20

Aby obliczyć moc grzewczą dla niestandardowych parametrów zasilania należy podzielić moc grzewczą dla parametru 75/65/20 przez wartość odczytaną z tabeli współczynników korekcyjnych.
Np. Szukamy mocy grzewczej dla grzejnika S6/60 dla parametru 70/50/20. Moc dla 75/65/20 wynosi 922 W. W tabeli współczynników korekcyjnych odczytujemy wartość współczynnika dla: tz = 70, tp = 50, temperatura pomieszczenia = 20. Dla tych parametrów współczynnik wynosi: 1,246.
Zatem: 922/1,246 ≈740 W

DECOR PRO

Współczynniki korekcyjne dla grzejników dekoracyjnych REGULUS-system DECOR

temperatura pomieszczenia
tztp581216202224
95900,490,510,550,580,620,650,67
850,510,530,570,610,650,680,70
800,530,550,590,630,680,710,74
750,550,580,620,660,720,750,78
700,570,600,650,700,750,780,82
90850,530,550,590,630,680,710,74
800,550,580,620,660,720,750,78
750,570,600,650,700,750,780,82
700,600,630,680,730,790,830,87
650,620,660,710,770,840,880,92
85800,570,600,650,700,750,780,82
750,600,630,680,730,790,830,87
700,620,660,710,770,840,880,92
650,650,690,750,810,890,930,98
600,680,720,780,860,940,991,04
80750,620,660,710,770,840,880,92
700,650,690,750,810,890,930,98
650,680,720,780,860,940,991,04
600,720,760,830,911,001,051,11
550,750,800,880,961,071,131,19
75700,680,720,780,860,940,991,04
650,720,760,830,911,001,051,11
600,750,800,880,961,071,131,19
550,790,850,931,031,141,211,29
500,840,900,991,101,231,311,39
70650,750,800,880,961,071,131,19
600,790,850,931,031,141,211,29
550,840,900,991,101,231,311,39
500,890,951,051,181,331,421,52
450,941,011,131,271,441,541,66
65600,840,900,991,101,231,311,39
550,890,951,051,181,331,421,52
500,941,011,131,271,441,541,66
451,001,081,211,371,571,691,84
60550,941,011,131,271,441,541,66
501,001,081,211,371,571,691,84
451,071,161,311,491,731,872,04
401,141,251,421,631,912,092,29
55501,071,161,311,491,731,872,04
451,141,251,421,631,912,092,29
401,231,351,541,802,142,352,61
351,331,471,692,002,412,683,01
50451,231,351,541,802,142,352,61
401,331,471,692,002,412,683,01
351,441,601,872,242,763,103,53
301,571,762,092,543,203,664,25
45401,441,601,872,242,763,103,53
351,571,762,092,543,203,664,25
301,731,952,352,923,794,435,27
40351,731,952,352,923,794,435,27
301,912,192,683,424,615,536,84

LEGENDA:
tz – temperatura zasilania
tp – temperatura powrotu

W opisie parametrów grzejnika tz występuje jako pierwsza wartość, tp jako druga, a tempertura pomieszczenia jako trzecia, np. 55/45/20

Aby obliczyć moc grzewczą dla niestandardowych parametrów zasilania należy podzielić moc grzewczą dla parametru 75/65/20 przez wartość odczytaną z tabeli współczynników korekcyjnych.
Np. Szukamy mocy grzewczej dla grzejnika S6/60 dla parametru 70/50/20. Moc dla 75/65/20 wynosi 922 W. W tabeli współczynników korekcyjnych odczytujemy wartość współczynnika dla: tz = 70, tp = 50, temperatura pomieszczenia = 20. Dla tych parametrów współczynnik wynosi: 1,246.
Zatem: 922/1,246 ≈740 W

DECOR VENT

Współczynniki korekcyjne dla grzejników dekoracyjnych REGULUS-system TOWER VENT

temperatura pomieszczenia
tztp581216202224
95900,490,510,550,580,620,650,67
850,510,530,570,610,650,680,70
800,530,550,590,630,680,710,74
750,550,580,620,660,720,750,78
700,570,600,650,700,750,780,82
90850,530,550,590,630,680,710,74
800,550,580,620,660,720,750,78
750,570,600,650,700,750,780,82
700,600,630,680,730,790,830,87
650,620,660,710,770,840,880,92
85800,570,600,650,700,750,780,82
750,600,630,680,730,790,830,87
700,620,660,710,770,840,880,92
650,650,690,750,810,890,930,98
600,680,720,780,860,940,991,04
80750,620,660,710,770,840,880,92
700,650,690,750,810,890,930,98
650,680,720,780,860,940,991,04
600,720,760,830,911,001,051,11
550,750,800,880,961,071,131,19
75700,680,720,780,860,940,991,04
650,720,760,830,911,001,051,11
600,750,800,880,961,071,131,19
550,790,850,931,031,141,211,29
500,840,900,991,101,231,311,39
70650,750,800,880,961,071,131,19
600,790,850,931,031,141,211,29
550,840,900,991,101,231,311,39
500,890,951,051,181,331,421,52
450,941,011,131,271,441,541,66
65600,840,900,991,101,231,311,39
550,890,951,051,181,331,421,52
500,941,011,131,271,441,541,66
451,001,081,211,371,571,691,84
60550,941,011,131,271,441,541,66
501,001,081,211,371,571,691,84
451,071,161,311,491,731,872,04
401,141,251,421,631,912,092,29
55501,071,161,311,491,731,872,04
451,141,251,421,631,912,092,29
401,231,351,541,802,142,352,61
351,331,471,692,002,412,683,01
50451,231,351,541,802,142,352,61
401,331,471,692,002,412,683,01
351,441,601,872,242,763,103,53
301,571,762,092,543,203,664,25
45401,441,601,872,242,763,103,53
351,571,762,092,543,203,664,25
301,731,952,352,923,794,435,27
40351,731,952,352,923,794,435,27
301,912,192,683,424,615,536,84

LEGENDA:
tz – temperatura zasilania
tp – temperatura powrotu

W opisie parametrów grzejnika tz występuje jako pierwsza wartość, tp jako druga, a tempertura pomieszczenia jako trzecia, np. 55/45/20

Aby obliczyć moc grzewczą dla niestandardowych parametrów zasilania należy podzielić moc grzewczą dla parametru 75/65/20 przez wartość odczytaną z tabeli współczynników korekcyjnych.
Np. Szukamy mocy grzewczej dla grzejnika S6/60 dla parametru 70/50/20. Moc dla 75/65/20 wynosi 922 W. W tabeli współczynników korekcyjnych odczytujemy wartość współczynnika dla: tz = 70, tp = 50, temperatura pomieszczenia = 20. Dla tych parametrów współczynnik wynosi: 1,246.
Zatem: 922/1,246 ≈740 W

VERTAGO

Współczynniki korekcyjne dla grzejników stojących REGULUS-system VERTAGO

temperatura pomieszczenia
tztp581216202224
95900.5750.5950.6240.6560.6920.7110.731
850.5920.6130.6440.6780.7160.7370.758
800.6090.6320.6650.7010.7420.7640.788
750.6280.6520.6870.7260.7700.7940.819
700.6480.6740.7110.7530.8000.8260.854
90850.6100.6330.6650.7020.7430.7650.788
800.6290.6530.6880.7270.7710.7950.820
750.6490.6740.7120.7540.8010.8270.854
700.6700.6970.7370.7820.8340.8620.892
650.6920.7220.7650.8140.8690.90.933
85800.6490.6750.7120.7540.8020.8280.855
750.6710.6980.7380.7830.8340.8630.893
700.6930.7220.7660.8140.8700.9010.934
650.7170.7490.7950.8480.9090.9420.978
600.7430.7770.8280.8850.9510.9881.028
80750.6940.7230.7670.8150.8710.9020.935
700.7180.7500.7960.8490.9100.9430.980
650.7440.7780.8290.8860.9520.9891.029
600.7720.8090.8640.9260.9991.0401.084
550.8030.8420.9020.9701.0501.0961.145
75700.7450.7790.830.8870.9530.9901.mar
650.7730.8100.8650.9271.0001.0411.085
600.8040.8430.9030.9711.0521.0971.146
550.8360.8790.9441.0201.1091.1591.215
500.8720.9190.9901.0741.1731.2291.292
70650.8050.8440.9040.9731.0531.0981.148
600.8370.8810.9461.0211.1101.1611.216
550.8730.9200.9921.0751.1741.2311.294
500.9120.9641.0421.1351.2461.3101.382
450.9551.0111.0981.2021.3271.4011.483
65600.8740.9210.9931.0771.1761.2331.295
550.9130.9651.0441.1361.2481.3121.383
500.9561.0131.1001.2041.3291.4031.485
60550.9571.0141.1011.2051.3311.4051.487
501.0041.0671.1641.2811.4241.5091.604
451.0561.1261.2341.3671.5321.6301.742
401.1131.1911.3141.4651.6571.7721.906
55501.0581.1271.2361.3691.5341.6331.745
451.1151.1931.3161.4681.6591.7751.909
401.1791.2671.4071.5821.8071.9462.108
351.2521.3511.5111.7151.9842.1532.354
50451.1821.2691.4091.5851.8101.9492.112
401.2541.3531.5141.7181.9872.1572.358
351.3361.4491.6361.8772.2042.4142.670
301.429sty.561.7782.0692.4732.7423.078
45401.3381.4521.6391.8812.2082.4192.675
351.4321.5631.7822.0732.4782.7483.084
301.5401.6931.9532.3082.8243.1813.642
40351.5431.6971.9572.3142.8313.188mar.65
301.6691.8512.1662.6113.2923.7884.462

LEGENDA:
tz – temperatura zasilania
tp – temperatura powrotu

W opisie parametrów grzejnika tz występuje jako pierwsza wartość, tp jako druga, a tempertura pomieszczenia jako trzecia, np. 55/45/20

Aby obliczyć moc grzewczą dla niestandardowych parametrów zasilania należy podzielić moc grzewczą dla parametru 75/65/20 przez wartość odczytaną z tabeli współczynników korekcyjnych.
Np. Szukamy mocy grzewczej dla grzejnika S6/60 dla parametru 70/50/20. Moc dla 75/65/20 wynosi 922 W. W tabeli współczynników korekcyjnych odczytujemy wartość współczynnika dla: tz = 70, tp = 50, temperatura pomieszczenia = 20. Dla tych parametrów współczynnik wynosi: 1,246.
Zatem: 922/1,246 ≈740 W

S-CORNER

Współczynniki korekcyjne dla grzejników stojących narożnych REGULUS-system S-CORNER

temperatura pomieszczenia
tztp581216202224
95900.5750.5950.6240.6560.6920.7110.731
850.5920.6130.6440.6780.7160.7370.758
800.6090.6320.6650.7010.7420.7640.788
750.6280.6520.6870.7260.7700.7940.819
700.6480.6740.7110.7530.8000.8260.854
90850.6100.6330.6650.7020.7430.7650.788
800.6290.6530.6880.7270.7710.7950.820
750.6490.6740.7120.7540.8010.8270.854
700.6700.6970.7370.7820.8340.8620.892
650.6920.7220.7650.8140.8690.90.933
85800.6490.6750.7120.7540.8020.8280.855
750.6710.6980.7380.7830.8340.8630.893
700.6930.7220.7660.8140.8700.9010.934
650.7170.7490.7950.8480.9090.9420.978
600.7430.7770.8280.8850.9510.9881.028
80750.6940.7230.7670.8150.8710.9020.935
700.7180.7500.7960.8490.9100.9430.980
650.7440.7780.8290.8860.9520.9891.029
600.7720.8090.8640.9260.9991.0401.084
550.8030.8420.9020.9701.0501.0961.145
75700.7450.7790.830.8870.9530.9901.mar
650.7730.8100.8650.9271.0001.0411.085
600.8040.8430.9030.9711.0521.0971.146
550.8360.8790.9441.0201.1091.1591.215
500.8720.9190.9901.0741.1731.2291.292
70650.8050.8440.9040.9731.0531.0981.148
600.8370.8810.9461.0211.1101.1611.216
550.8730.9200.9921.0751.1741.2311.294
500.9120.9641.0421.1351.2461.3101.382
450.9551.0111.0981.2021.3271.4011.483
65600.8740.9210.9931.0771.1761.2331.295
550.9130.9651.0441.1361.2481.3121.383
500.9561.0131.1001.2041.3291.4031.485
60550.9571.0141.1011.2051.3311.4051.487
501.0041.0671.1641.2811.4241.5091.604
451.0561.1261.2341.3671.5321.6301.742
401.1131.1911.3141.4651.6571.7721.906
55501.0581.1271.2361.3691.5341.6331.745
451.1151.1931.3161.4681.6591.7751.909
401.1791.2671.4071.5821.8071.9462.108
351.2521.3511.5111.7151.9842.1532.354
50451.1821.2691.4091.5851.8101.9492.112
401.2541.3531.5141.7181.9872.1572.358
351.3361.4491.6361.8772.2042.4142.670
301.429sty.561.7782.0692.4732.7423.078
45401.3381.4521.6391.8812.2082.4192.675
351.4321.5631.7822.0732.4782.7483.084
301.5401.6931.9532.3082.8243.1813.642
40351.5431.6971.9572.3142.8313.188mar.65
301.6691.8512.1662.6113.2923.7884.462

LEGENDA:
tz – temperatura zasilania
tp – temperatura powrotu

W opisie parametrów grzejnika tz występuje jako pierwsza wartość, tp jako druga, a tempertura pomieszczenia jako trzecia, np. 55/45/20

Aby obliczyć moc grzewczą dla niestandardowych parametrów zasilania należy podzielić moc grzewczą dla parametru 75/65/20 przez wartość odczytaną z tabeli współczynników korekcyjnych.
Np. Szukamy mocy grzewczej dla grzejnika S6/60 dla parametru 70/50/20. Moc dla 75/65/20 wynosi 922 W. W tabeli współczynników korekcyjnych odczytujemy wartość współczynnika dla: tz = 70, tp = 50, temperatura pomieszczenia = 20. Dla tych parametrów współczynnik wynosi: 1,246.
Zatem: 922/1,246 ≈740 W

SOLO

Współczynniki korekcyjne dla grzejników kanałowych REGULUS-system CANAL typ SOLO

Temperatura pomieszczenia
tztp581216202224
95900.480.500.530.570.610.630.66
850.500.520.560.600.640.670.69
800.520.540.580.630.680.700.73
750.540.570.610.660.710.740.78
700.570.600.640.700.760.790.83
90850.520.540.580.620.670.700.73
800.540.570.610.650.710.740.77
750.560.590.640.690.750.780.82
700.590.620.670.730.790.830.87
650.620.660.710.770.850.890.93
85800.560.590.630.690.740.780.81
750.590.620.670.720.790.820.86
700.610.650.700.760.830.880.92
650.650.680.740.810.890.940.99
600.680.720.790.870.961.011.07
80750.610.650.700.760.830.870.91
700.640.680.740.800.880.930.97
650.680.720.780.850.940.991.05
600.710.760.830.911.011.071.13
550.760.810.890.981.101.171.24
75700.670.710.780.850.930.981.04
650.710.750.820.901.061.12
600.750.800.880.971.081.141.21
550.790.850.941.041.171.241.33
500.850.911.011.131.281.371.47
70650.740.790.870.961.071.131.20
600.790.840.931.031.151.221.30
550.830.900.991.111.251.331.43
500.890.961.071.211.371.471.59
450.961.041.171.331.531.651.80
65600.830.890.981.101.231.321.41
550.880.951.061.181.341.441.55
500.941.021.141.291.481.591.72
60550.931.011.131.271.461.561.69
501,001.091.221.391.601.741.89
451.081.171.331.531.801.962.15
401.171.281.471.722.052.262.52
55501.071.161.321.511.761.912.09
451.151.261.441.671.972.162.39
401.251.381.591.872.262.512.81
351.371.531.792.152.673.023.47
50451.231.361.561.832.192.422.70
401.341.491.742.062.522.823.19
351.481.661.962.382.993.423.97
301.651.872.262.833.754.465.48
45401.461.621.912.302.863.233.70
351.601.812.162.663.413.944.65
301.802.052.513.194.315.206.50
40351.762,002.423.033.994.695.64
301.972.272.823.665.096.268.03

LEGENDA:
tz – temperatura zasilania
tp – temperatura powrotu

W opisie parametrów grzejnika tz występuje jako pierwsza wartość, tp jako druga, a tempertura pomieszczenia jako trzecia, np. 55/45/20

Aby obliczyć moc grzewczą dla niestandardowych parametrów zasilania należy podzielić moc grzewczą dla parametru 75/65/20 przez wartość odczytaną z tabeli współczynników korekcyjnych.
Np. Szukamy mocy grzewczej dla grzejnika S6/60 dla parametru 70/50/20. Moc dla 75/65/20 wynosi 922 W. W tabeli współczynników korekcyjnych odczytujemy wartość współczynnika dla: tz = 70, tp = 50, temperatura pomieszczenia = 20. Dla tych parametrów współczynnik wynosi: 1,246.
Zatem: 922/1,246 ≈740 W

DUO 100

Współczynniki korekcyjne dla grzejników kanałowych REGULUS-system CANAL typ DUO 100

temperatura pomieszczenia
tztp581216202224
9590 0,440,470,500.540.580.610.63
850.460.490.520.570.610.640.67
800.480.510.550.600.650.680.71
750.510.540.580.630.690.720.76
700.540.570.620.670.740.770.81
90850.480.510.550.590.650.670.71
800.510.530.580.630.680.710.75
750.530.560.610.660.730.760.80
700.560.590.650.710.780.810.86
650.590.630.690.750.830.880.93
85800.530.560.610.660.720.760.79
750.560.590.640.700.770.810.85
700.580.620.680.740.820.860.91
650.620.660.720.790.880.930.99
600.660.700.770.850.951.011.07
80750.580.620.670.740.810.860.90
700.610.650.710.790.870.920.97
650.650.690.760.840.940.991.05
600.690.740.810.911.011.081.15
550.740.790.880.981.111.181.27
75700.650.690.760.830.930.981.04
650.680.730.810.891,001.061.13
600.730.780.860.961.081.161.23
550.780.840.931.051.191.271.36
500.830.901.011.151.311.421.53
70650.720.770.860.951.071.141.22
600.770.830.921.031.171.251.34
550.820.890.991.121.281.371.48
500.880.961.081.231.421.531.66
450.951.041.181.361.591.741.91
65600.810.880.981.111.261.351.45
550.870.941.061.201.381.491.61
500.941.021.161.321.541.671.82
60550.931.011.141.301.511.641.78
501,001.091.251.441.681.832.01
451.081.191.371.601.902.092.32
401.191.321.531.812.202.452.76
55501.071.181.351.571.862.042.25
451.171.291.491.762.112.332.61
401.281.421.671.992.452.753.12
351.421.591.902.322.943.373.93
50451.261.401.641.952.372.642.98
401.381.551.832.222.763.133.58
351.541.742.092.593.333.864.56
301.731.992.453.144.285.176.49
45401.511.702.042.503.173.634.22
351.681.922.332.933.854.525.42
301.902.202.753.584.996.137.84
40351.862.142.643.394.585.476.70
302.112.463.134.175.997.519.89

LEGENDA:
tz – temperatura zasilania
tp – temperatura powrotu

W opisie parametrów grzejnika tz występuje jako pierwsza wartość, tp jako druga, a tempertura pomieszczenia jako trzecia, np. 55/45/20

Aby obliczyć moc grzewczą dla niestandardowych parametrów zasilania należy podzielić moc grzewczą dla parametru 75/65/20 przez wartość odczytaną z tabeli współczynników korekcyjnych.
Np. Szukamy mocy grzewczej dla grzejnika S6/60 dla parametru 70/50/20. Moc dla 75/65/20 wynosi 922 W. W tabeli współczynników korekcyjnych odczytujemy wartość współczynnika dla: tz = 70, tp = 50, temperatura pomieszczenia = 20. Dla tych parametrów współczynnik wynosi: 1,246.
Zatem: 922/1,246 ≈740 W

QUATTRO

Współczynniki korekcyjne dla grzejników kanałowych REGULUS-system CANAL typ QUATTRO 150

Temperatura pomieszczenia
tztp581216202224
95900.470.490.530.560.600.630.65
850.490.510.550.590.630.660.69
800.510.540.570.620.670.700.77
750.530.560.600.650.710.740.77
700.560.590.640.690.750.790.82
90850.510.530.570.620.670.690.72
800.530.560.600.650.700.730.76
750.550.580.630.680.740.780.81
700.580.620.660.720.790.830.87
650.610.650.700.770.840.880.93
85800.550.580.630.680.740.770.81
750.580.610.660.720.780.820.86
700.610.640.700.760.830.870.92
650.640.680.740.810.890.930.99
600.680.720.790.860.961.011.07
80750.600.640.690.750.830.870.91
700.630.670.730.800.880.920.97
650.670.710.780.850.940.991.05
600.710.750.830.911.011.071.14
550.750.800.880.981.101.171.25
75700.670.710.770.840.930.981.04
650.700.750.820.901.061.12
600.740.790.870.971.081.141.22
550.790.850.931.041.171.251.33
500.840.911.011.131.291.381.48
70650.740.790.870.961.071.131.20
600.780.840.921.031.151.221.31
550.830.890.991.111.251.341.44
500.890.961.071.211.381.481.60
450.961.041.171.331.541.671.82
65600.830.890.981.101.241.321.41
550.880.951.061.191.351.451.56
500.941.021.141.301.491.611.74
60550.931.011.131.281.471.581.71
501,001.091.221.401.621.751.91
451.081.181.341.551.821.982.18
401.171.291.481.742.082.302.57
55501.071.161.321.521.781.942.12
451.151.261.451.682,002.202.43
401.251.391.611.902.302.552.87
351.381.541.812.182.723.093.56
50451.241.371.581.852.222.462.75
401.351.501.752.092.572.883.27
351.491.671.982.423.063.504.08
301.671.892.302.903.854.605.68
45401.471.641.942.342.923.313.80
351.621.832.202.713.504.064.80
301.822.082.553.274.445.376.76
40351.782.022.463.104.104.845.84
302,002.312.883.765.266.508.38

 

Współczynniki korekcyjne dla grzejników kanałowych REGULUS-system CANAL typ QUATTRO 200/270

Temperatura pomieszczenia#colspan#
tztp581216202224
95900.460.480.510.550.590.620.64
850.480.500.540.580.620.650.69
800.500.520.560.610.660.690.72
750.520.550.590.640.700.730.76
700.550.580.630.680.740.780.82
90850.500.520.560.600.660.680.71
800.520.550.590.640.690.720.76
750.540.570.620.670.730.770.81
700.570.600.650.710.780.820.86
650.600.640.690.760.840.880.93
85800.540.570.620.670.730.760.80
750.570.600.650.710.770.810.85
700.600.630.690.750.830.870.91
650.630.670.730.800.880.930.99
600.670.710.780.860.951.011.07
80750.590.630.680.750.820.860.91
700.620.660.720.790.870.920.97
650.660.700.770.850.940.991.05
600.700.750.820.911.011.071.14
550.740.800.880.981.101.181.26
75700.660.700.760.840.930.981.04
650.690.740.810.901.061.12
600.730.790.870.961.081.151.22
550.780.840.931.041.181.261.35
500.840.901.011.141.301.401.51
70650.730.780.860.961.071.141.21
600.770.830.921.031.161.231.32
550.830.890.991.111.261.351.46
500.880.961.071.221.401.511.63
450.951.041.181.351.571.701.86
65600.820.880.981.101.251.341.43
550.870.951.061.201.371.471.58
450.941.021.151.311.511.641.78
60550.931.011.141.291.491.601.74
501.001.091.231.421.641.791.96
451.081.191.351.571.862.042.25
401.181.301.511.772.142.372.66
55501.071.171.341.541.821.982.18
451.161.281.471.722.052.262.51
401.261.401.641.942.372.642.98
351.401.571.852.252.823.223.73
50451.251.381.601.902.292.552.86
401.371.521.792.152.662.993.41
351.511.702.042.503.193.674.30
301.701.942.373.014.054.866.05
45401.491.671.982.413.043.464.00
351.651.872.262.823.664.275.08
301.862.142.643.414.705.727.25
40351.822.0792.553.244.325.136.24
302.052.382.993.955.606.969.07

LEGENDA:
tz – temperatura zasilania
tp – temperatura powrotu

W opisie parametrów grzejnika tz występuje jako pierwsza wartość, tp jako druga, a tempertura pomieszczenia jako trzecia, np. 55/45/20

Aby obliczyć moc grzewczą dla niestandardowych parametrów zasilania należy podzielić moc grzewczą dla parametru 75/65/20 przez wartość odczytaną z tabeli współczynników korekcyjnych.
Np. Szukamy mocy grzewczej dla grzejnika S6/60 dla parametru 70/50/20. Moc dla 75/65/20 wynosi 922 W. W tabeli współczynników korekcyjnych odczytujemy wartość współczynnika dla: tz = 70, tp = 50, temperatura pomieszczenia = 20. Dla tych parametrów współczynnik wynosi: 1,246.
Zatem: 922/1,246 ≈740 W

TRIOVENT

Współczynniki korekcyjne dla grzejników kanałowych REGULUS-system CANAL typ TRIOVENT

temperatura pomieszczenia
tztp581216202224
95900,530,550,580,620,660,680,70
850,550,570,600,640,680,710,73
800,570,590,630,670,710,740,76
750,590,610,650,690,740,770,80
700,610,640,680,720,780,810,84
90850,570,590,630,670,710,740,76
800,590,610,650,690,740,770,80
750,610,640,680,720,780,810,84
700,630,660,710,760,810,840,88
650,660,690,740,790,850,890,93
85800,610,640,680,720,780,810,84
750,630,660,710,760,810,840,88
700,660,690,740,790,850,890,93
650,680,720,770,830,900,940,98
600,710,750,810,870,950,991,03
80750,660,690,740,790,850,890,93
700,680,720,770,830,900,940,98
650,710,750,810,870,950,991,03
600,740,780,840,921,001,051,10
550,780,820,890,971,061,111,17
75700,710,750,810,870,950,991,03
650,740,780,840,921,001,051,10
600,780,820,890,971,061,111,17
550,810,860,941,021,131,191,25
500,850,910,991,091,201,271,34
70650,780,820,890,971,061,111,17
600,810,860,941,021,131,191,25
550,850,910,991,091,201,271,34
500,900,961,051,161,291,361,45
450,951,011,111,241,391,471,57
65600,850,910,991,091,201,271,34
550,900,961,051,161,291,361,45
500,951,011,111,241,391,471,57
451,001,071,191,331,501,601,72
60550,951,011,111,241,391,471,57
501,001,071,191,331,501,601,72
451,061,141,271,431,631,751,89
401,131,221,361,551,781,932,10
55501,061,141,271,431,631,751,89
451,131,221,361,551,781,932,10
401,201,311,471,691,972,152,35
351,291,411,601,852,192,412,67
50451,201,311,471,691,972,152,35
401,291,411,601,852,192,412,67
351,391,521,752,052,472,753,09
301,501,661,932,302,833,193,64
45401,391,521,752,052,472,753,09
351,501,661,932,302,833,193,64
301,631,822,152,603,293,774,42
40351,631,822,152,603,293,774,42
301,782,012,413,003,924,615,57

LEGENDA:
tz – temperatura zasilania
tp – temperatura powrotu

W opisie parametrów grzejnika tz występuje jako pierwsza wartość, tp jako druga, a tempertura pomieszczenia jako trzecia, np. 55/45/20

Aby obliczyć moc grzewczą dla niestandardowych parametrów zasilania należy podzielić moc grzewczą dla parametru 75/65/20 przez wartość odczytaną z tabeli współczynników korekcyjnych.
Np. Szukamy mocy grzewczej dla grzejnika S6/60 dla parametru 70/50/20. Moc dla 75/65/20 wynosi 922 W. W tabeli współczynników korekcyjnych odczytujemy wartość współczynnika dla: tz = 70, tp = 50, temperatura pomieszczenia = 20. Dla tych parametrów współczynnik wynosi: 1,246.
Zatem: 922/1,246 ≈740 W

QUATTROVENT

Współczynniki korekcyjne dla grzejników kanałowych REGULUS-system CANAL typ QUATTROVENT

temperatura pomieszczenia
tztp581216202224
95900,560,580,610,640,680,700,72
850,570,600,630,660,700,720,75
800,590,620,650,690,730,750,78
750,610,640,670,710,760,790,81
700,630,660,700,740,790,820,85
90850,590,620,650,690,730,750,78
800,610,640,670,710,760,790,81
750,630,660,700,740,790,820,85
700,650,680,720,770,830,860,89
650,680,710,750,810,860,900,93
85800,630,660,700,740,790,820,85
750,650,680,720,770,830,860,89
700,680,710,750,810,860,900,93
650,700,740,790,840,910,940,98
600,730,770,820,880,950,991,03
80750,680,710,750,810,860,900,93
700,700,740,790,840,910,940,98
650,730,770,820,880,950,991,03
600,760,800,860,921,001,041,09
550,790,830,900,971,061,101,16
75700,730,770,820,880,950,991,03
650,760,800,860,921,001,041,09
600,790,830,900,971,061,101,16
550,830,870,941,021,121,171,23
500,860,910,991,081,191,251,31
70650,790,830,900,971,061,101,16
600,830,870,941,021,121,171,23
550,860,910,991,081,191,251,31
500,910,961,041,141,261,331,41
450,951,011,101,221,351,431,52
65600,860,910,991,081,191,251,31
550,910,961,041,141,261,331,41
500,951,011,101,221,351,431,52
451,001,071,171,301,451,551,65
60550,951,011,101,221,351,431,52
501,001,071,171,301,451,551,65
451,061,131,251,391,571,681,80
401,121,201,331,501,711,841,98
55501,061,131,251,391,571,681,80
451,121,201,331,501,711,841,98
401,191,281,431,621,872,022,20
351,261,371,551,772,072,252,48
50451,191,281,431,621,872,022,20
401,261,371,551,772,072,252,48
351,351,471,681,942,312,542,83
301,451,601,842,162,612,913,30
45401,351,471,681,942,312,542,83
351,451,601,842,162,612,913,30
301,571,742,022,423,003,413,94
40351,571,742,022,423,003,413,94
301,711,912,252,753,534,104,88

LEGENDA:
tz – temperatura zasilania
tp – temperatura powrotu

W opisie parametrów grzejnika tz występuje jako pierwsza wartość, tp jako druga, a tempertura pomieszczenia jako trzecia, np. 55/45/20

Aby obliczyć moc grzewczą dla niestandardowych parametrów zasilania należy podzielić moc grzewczą dla parametru 75/65/20 przez wartość odczytaną z tabeli współczynników korekcyjnych.
Np. Szukamy mocy grzewczej dla grzejnika S6/60 dla parametru 70/50/20. Moc dla 75/65/20 wynosi 922 W. W tabeli współczynników korekcyjnych odczytujemy wartość współczynnika dla: tz = 70, tp = 50, temperatura pomieszczenia = 20. Dla tych parametrów współczynnik wynosi: 1,246.
Zatem: 922/1,246 ≈740 W

SOLOVENT

Współczynniki korekcyjne dla grzejników ściennych REGULUS-system REGULLUS

tztp581216202224
95900,550,570,600,630,670,690,71
850,570,590,620,660,700,720,74
800,580,610,640,680,720,750,77
750,600,630,670,710,750,780,81
700,620,650,690,740,790,810,84
90850,580,610,640,680,720,750,77
800,600,630,670,710,750,780,81
750,620,650,690,740,790,810,84
700,650,680,720,770,820,850,89
650,670,700,750,800,860,890,93
85800,620,650,690,740,790,810,84
750,650,680,720,770,820,850,89
700,670,700,750,800,860,890,93
650,700,730,780,840,900,940,98
600,720,760,810,880,950,991,03
80750,670,700,750,800,860,890,93
700,700,730,780,840,900,940,98
650,720,760,810,880,950,991,03
600,750,790,850,921,001,051,09
550,790,830,890,971,061,111,16
75700,720,760,810,880,950,991,03
650,750,790,850,921,001,051,09
600,790,830,890,971,061,111,16
550,820,870,941,021,121,181,24
500,860,910,991,081,191,251,33
70650,790,830,890,971,061,111,16
600,820,870,941,021,121,181,24
550,860,910,991,081,191,251,33
500,900,961,051,151,271,341,42
450,951,011,111,221,361,451,54
65600,860,910,991,081,191,251,33
550,900,961,051,151,271,341,42
500,951,011,111,221,361,451,54
451,001,071,181,311,471,561,67
60550,951,011,111,221,361,451,54
501,001,071,181,311,471,561,67
451,061,131,251,401,591,701,83
401,121,211,341,511,731,872,02
55501,061,131,251,401,591,701,83
451,121,211,341,511,731,872,02
401,191,291,451,641,902,062,25
351,271,381,561,802,112,312,54
50451,191,291,451,641,902,062,25
401,271,381,561,802,112,312,54
351,361,491,701,982,362,612,92
301,471,621,872,202,683,003,41
45401,361,491,701,982,362,612,92
351,471,621,872,202,683,003,41
301,591,762,062,483,103,534,09
40351,591,762,062,483,103,534,09
301,731,942,312,833,654,265,10

LEGENDA:
tz – temperatura zasilania
tp – temperatura powrotu

W opisie parametrów grzejnika tz występuje jako pierwsza wartość, tp jako druga, a tempertura pomieszczenia jako trzecia, np. 55/45/20

Aby obliczyć moc grzewczą dla niestandardowych parametrów zasilania należy podzielić moc grzewczą dla parametru 75/65/20 przez wartość odczytaną z tabeli współczynników korekcyjnych.
Np. Szukamy mocy grzewczej dla grzejnika S6/60 dla parametru 70/50/20. Moc dla 75/65/20 wynosi 922 W. W tabeli współczynników korekcyjnych odczytujemy wartość współczynnika dla: tz = 70, tp = 50, temperatura pomieszczenia = 20. Dla tych parametrów współczynnik wynosi: 1,246.
Zatem: 922/1,246 ≈740 W

TETRAVENT

Współczynniki korekcyjne dla grzejników ściennych REGULUS-system REGULLUS

temperatura pomieszczenia
tztp581216202224
95900,550,570,600,640,670,690,72
850,570,590,620,660,700,720,74
800,590,610,650,680,730,750,78
750,610,630,670,710,760,780,81
700,630,650,690,740,790,820,85
90850,590,610,650,680,730,750,78
800,610,630,670,710,760,780,81
750,630,650,690,740,790,820,85
700,650,680,720,770,820,850,89
650,670,700,750,800,860,900,93
85800,630,650,690,740,790,820,85
750,650,680,720,770,820,850,89
700,670,700,750,800,860,900,93
650,700,730,780,840,900,940,98
600,730,760,820,880,950,991,03
80750,670,700,750,800,860,900,93
700,700,730,780,840,900,940,98
650,730,760,820,880,950,991,03
600,760,800,850,921,001,041,09
550,790,830,900,971,061,111,16
75700,730,760,820,880,950,991,03
650,760,800,850,921,0001,041,09
600,790,830,900,971,061,111,16
550,820,870,941,021,121,171,23
500,860,910,991,081,191,251,32
70650,790,830,900,971,061,111,16
600,820,870,941,021,121,171,23
550,860,910,991,081,191,251,32
500,900,961,041,151,271,341,42
450,951,011,111,221,361,441,53
65600,860,910,991,081,191,251,32
550,900,961,041,151,271,341,42
500,951,011,111,221,361,441,53
451,001,071,171,301,461,561,66
60550,951,011,111,221,361,441,53
501,001,071,171,301,461,561,66
451,061,131,251,401,581,691,82
401,121,201,341,511,721,852,00
55501,061,131,251,401,581,691,82
451,121,201,341,511,721,852,00
401,191,281,441,631,892,052,23
351,271,381,561,782,092,282,51
50451,191,281,441,631,892,052,23
401,271,381,561,782,092,282,51
351,361,481,691,962,342,582,88
301,461,611,852,182,652,963,36
45401,361,481,691,962,342,582,88
351,461,611,852,182,652,963,36
301,581,752,052,453,053,474,02
40351,581,752,052,453,053,474,02
301,721,922,282,803,594,185,00

LEGENDA:
tz – temperatura zasilania
tp – temperatura powrotu

W opisie parametrów grzejnika tz występuje jako pierwsza wartość, tp jako druga, a tempertura pomieszczenia jako trzecia, np. 55/45/20

Aby obliczyć moc grzewczą dla niestandardowych parametrów zasilania należy podzielić moc grzewczą dla parametru 75/65/20 przez wartość odczytaną z tabeli współczynników korekcyjnych.
Np. Szukamy mocy grzewczej dla grzejnika S6/60 dla parametru 70/50/20. Moc dla 75/65/20 wynosi 922 W. W tabeli współczynników korekcyjnych odczytujemy wartość współczynnika dla: tz = 70, tp = 50, temperatura pomieszczenia = 20. Dla tych parametrów współczynnik wynosi: 1,246.
Zatem: 922/1,246 ≈740 W

OKTOVENT

Współczynniki korekcyjne dla grzejników ściennych REGULUS-system REGULLUS

temperatura pomieszczenia
tztp581216202224
95900,570,590,620,650,690,710,73
850,590,610,640,670,710,730,76
800,600,630,660,700,740,760,79
750,620,650,680,720,770,790,82
700,640,670,710,750,800,830,85
90850,600,630,660,700,740,760,79
800,620,650,680,720,770,790,82
750,640,670,710,750,800,830,85
700,670,690,730,780,830,860,89
650,690,720,760,810,870,900,93
85800,640,670,710,750,800,830,85
750,670,690,730,780,830,860,89
700,690,720,760,810,870,900,93
650,710,750,790,850,910,940,98
600,740,770,830,880,950,991,03
80750,690,720,760,810,870,900,93
700,710,750,790,850,910,940,98
650,740,770,830,880,950,991,03
600,770,810,860,931,001,041,09
550,800,840,900,971,051,101,15
75700,740,770,830,880,950,991,03
650,770,810,860,931,0001,041,09
600,800,840,900,971,051,101,15
550,830,880,941,021,111,161,22
500,870,920,991,081,181,241,30
70650,800,840,900,971,051,101,15
600,830,880,941,021,111,161,22
550,870,920,991,081,181,241,30
500,910,961,041,141,251,321,39
450,951,011,101,211,341,411,50
65600,870,920,991,081,181,241,30
550,910,961,041,141,251,321,39
500,951,011,101,211,341,411,50
451,001,061,161,281,431,521,62
60550,951,011,101,211,341,411,50
501,001,061,161,281,431,521,62
451,051,121,241,371,541,641,76
401,111,191,321,471,671,791,93
55501,051,121,241,371,541,641,76
451,111,191,321,471,671,791,93
401,181,271,411,591,821,972,14
351,251,351,521,732,012,182,39
50451,181,271,411,591,821,972,14
401,251,351,521,732,012,182,39
351,341,451,641,892,232,452,72
301,431,571,792,092,512,803,15
45401,341,451,641,892,232,452,72
351,431,571,792,092,512,803,15
301,541,701,972,342,883,253,73
40351,541,701,972,342,883,253,73
301,671,862,182,653,363,884,59

LEGENDA:
tz – temperatura zasilania
tp – temperatura powrotu

W opisie parametrów grzejnika tz występuje jako pierwsza wartość, tp jako druga, a tempertura pomieszczenia jako trzecia, np. 55/45/20

Aby obliczyć moc grzewczą dla niestandardowych parametrów zasilania należy podzielić moc grzewczą dla parametru 75/65/20 przez wartość odczytaną z tabeli współczynników korekcyjnych.
Np. Szukamy mocy grzewczej dla grzejnika S6/60 dla parametru 70/50/20. Moc dla 75/65/20 wynosi 922 W. W tabeli współczynników korekcyjnych odczytujemy wartość współczynnika dla: tz = 70, tp = 50, temperatura pomieszczenia = 20. Dla tych parametrów współczynnik wynosi: 1,246.
Zatem: 922/1,246 ≈740 W